Transcript
The digital inputs each have five terminals: DI–, DI+, Vcc (+5V), shield, and ground. Table 2-3 identifies the pin numbers for the digital inputs. Table 2-3: ACU DI Connections Pin Number Description 1 Shield 2 Ground 3 DI - 4 DI + 5 Vcc (+5v) In an inactive state, DI– should be pulled low (connected to ground) and DI+ pulled high (connected to Vcc). If either of those connections is broken, the digital input will signal alarm state. For the installation shown in Figure 2-1, connect a normally open magnetic switch between DI– and ground of DI_1. Put a jumper between DI+ and Vcc. (Or, you could put the magnetic switch between DI+ and Vcc, and the jumper between DI– and ground. The effect is the same.) Connect the wire’s shield, if any, to the shield terminal. Digital IN 1 (DI_1) Vcc DI+ DI- Gnd Introduction Wiring the Digital Inputs (DI_1 and DI_2) Shd Magnetic Door Sensor When contact is broken, DI_1 enters alarm state and can trigger DO_2 to sound alarm. In the installation being described, DI_2 is not used. Place jumpers between DI– and ground, and between DI+ and Vcc, of DI_2 to disable it. Digital IN 2 (DI_2) Vcc DI+ DI- Gnd Shd DI_2 not used. DI+ and DI- connected to power and ground to prevent ACU from entering alarm state. Accu-Time® Series 7000 Access Control Unit User’s Guide 2-8