Download Turck AS-interface Industrial I/O
Transcript
TURCK Industrial I/O AS-interface® Products Features AS-I masters and gateways are available with one or two supported AS-I networks, referred to as “single masters” and “double masters”. Double masters can be used to save cost and cabinet space where the system being installed is too large (physically or due to the number of slaves) for one AS-I network. The master and power supply may be connected anywhere along the network, but should be located next to each other. Slaves and repeaters should not be connected between the master and the power supply, as doing so disables some diagnostic features (such as duplicate address detection and ground fault detection). An example of a system with the “A-style” power supply (gateway is powered from the AS-I power supply) is shown here. To higher level network A Style AS-I power supply (30 VDC, decoupled) AS-I Network 1 (62 slaves max.) M5 TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708 www.turck.com Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com