Download - Eurotherm
Transcript
- Maximum value of integral time calculated by SMART algorithm - [r.L04] This parameter is available only when smart function is configured (“Sñ.Fn” [C.G01] = “Enb”) Range: from “ti.Lo” [r.L03] to 20.00 mm.ss - Minimum value of integral time calculated by SMART algorithm - [r.L03] This parameter is available only when smart function is configured (“Sñ.Fn” [C.G01] = “Enb”) Range: from 00.01 mm.ss to “ti.Hi” [r.L04]. - Relative gain of the secondary output calculated by SMART algorithm - [r.L05] This parameter is available only when smart function is configured (“Sñ.Fn” [C.G01] = “Enb”) and a secondary control output (without split range) is configured. Range: OFF = Smart algorithm does not calculate “r.Gn” [r.d06] value. On = Smart algorithm calculates “r.Gn” [r.d06] value. Gr.Hd - Maximum value of proportional band calculated by SMART algorithm - [r.L02] This parameter is available only when smart function is configured (“Sñ.Fn” [C.G01] = “Enb”) Range: from “Pb.Lo” [r.L01] to 999.0% NOTE: The resolution on “Pb.Hi” value will be equal to 0.1% up to 10.0% and 1% up to 999.0 101 Xkc-1-C0.P65 101 5/29/02, 11:59 AM