Download - Eurotherm
Transcript
Switching mode: isolated zero crossing type. Rated current: from 50 mA to 1 A. Rated voltage: from 24 VRMS to 240 VRMS -10 % +15 % (50/ 60Hz) Load type: resistive load only NOTES 1) To avoid electrical shock, connect power line at the end of the wiring procedure. 2) For power connections use No 16 AWG or larger wires rated for at last 75 °C. 3) Use copper conductors only. 4) Don’t run input wires together with power cables. 5) This output is not fuse protected. Please, provide it externally using a fuse with a I2t equal to128. E.4) SERVOMOTOR OUTPUT 29 30 31 s (Open the valve) Power line Servomotor t (Close the valve) s (Open) Feedback potentiometer 12 13 14 t (Close) Shield Fig. 15 SERVOMOTOR OUTPUT WIRING 15 Xkc-1-C0.P65 15 5/29/02, 11:59 AM