8.3
Installation on the floor (refer to table § 8.1)
The location of the cable trough is defined as
a function of the type of FBX to be installed
and the position of this switchboard in the
room.
In case of a lateral cable trough, fit
longitudinal irons to support the right and
left-hand uprights of the switchboard.
The support irons to be used are of
the 100 mm min. IPN type.
Example for a floor opening cable trough
(dimensions in mm)
Evacuation of the cables via
the cable trough
70 mm min.**
175
C1
619
**Switchboard side-by-side
with the wall with side deflector
600
Depth of the
cable trough
Example for a lateral cable trough
(dimensions in mm)
Evacuation of the cables via
the cable trough
Support iron
175
ÄÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄ
Support iron
70 mm min.**
C1
Depth of the
cable trough
AMTNoT110-02 revision: 10
600
619
**Switchboard side-by-side
with the wall with side deflector
17