Download L-Switch User Manual
Transcript
L-Switch User Manual 12 LOYTEC 2.3 Mounting The device comes prepared for mounting on DIN rails following DIN EN 50 022.The device can be mounted in any position. However, an installation place with proper airflow must be selected to ensure that the L-Switch XP temperature does not exceed the specified range (see Section 11). 2.4 DIP Switch Setting The L-Switch XP uses 7 switches to select the mode of operation. The DIP switch assignment is shown in Table 1. For details see Chapter 4. DIP Switch # 1, 2 Function ON, ON: L-Switch XP switch mode Factory Default ON, ON ON, OFF: L-Switch XP repeater mode OFF, ON: L-Switch XP subnet learning OFF, OFF: Configured CEA-709 router 3 Bit-rate auto detection On/Off (RS-485 version only) ON 4 Must be OFF OFF 5 Must be OFF OFF 6 Must be OFF OFF 7 Must be OFF OFF Table 1: DIP switch settings for L-Switch XP 2.5 Power Supply The L-Switch XP can either be DC or AC powered (Table 2 to Table 3). Terminal Function 24 Earth Ground 25, 26 Power Inputs Note 12-35 VDC or 12-24 VAC ± 10% Table 2: Power Terminals for L-Switch XP multi-port LS-xxxxxCB Version 6.0 LOYTEC electronics GmbH