Download User Manual - Instrumentation Central
Transcript
Troubleshooting This section is designed to offer possible solutions should you encounter problems when using Commander 4.1. SYSTEM SPEED Scan rate per loop is approximately equal to the value programmed in Setup Communications. Default setting is 100mS (0.1 second) per loop. This allows the program to scan 128 loops in approximately 13 seconds. If a large number of graphs are opened or other Windows programs are using a large amount of Windows resources, the system and thus the scan rate, may slow down. Slower computers may not be able to scan at this rate as well. Slower computers need a larger Scan value. If the Scan value is too small Windows has a difficult time performing required housekeeping functions and errors can result particularly if RAM is low. COMMANDER CRASHED WITH A GENERAL PROTECTION FAULT Probably due to insufficient RAM memory installed in computer. 16 megabytes (16,000,000) of RAM is required to reliably run Commander. Computer should be rebooted after such an error. Try not running as many programs at the same time if system speed degrades or if General Protection Faults occur. MESSAGE “NEED TO CONFIGURE LOOPS” APPEARS ON MAIN SCREEN No loops have been defined. Must define loops before Commander will operate. Select Setup Menu from Main Screen, then choose Define Loops. See: Defining Loops MESSAGE “NOT A VALID COMMS PORT” APPEARS ON MAIN SCREEN One or more of the Comms Ports, as defined in Communications Setup, is not a valid Comms Port. See: Communications Setup MESSAGE “LICENSE EXPIRED” APPEARS ON MAIN SCREEN License to use Commander has expired. You must call your software supplier for the required access number to continue using Commander. See: Software RegistrationMESSAGE “CHANNEL # XXX OFF LINE” APPEARS ON MAIN SCREEN (WEST ASCII) MESSAGE “MB CHANNEL # XXX (ERR-2)” MODBUS Indicates that the identified loop is not responding to Commander’s transmissions. This could be caused by: Wrong channel being programmed in the instrument Invalid entry in Define Loops. Wrong Comms Port ID or other parameters in Communications Setup. Bad wiring to control’s Comms Port Interface converter not wired or configured properly, or not of the proper type 62