Download View / the Complete Manual
Transcript
Chapter 5: GS1 Modbus Communications Step 4: Configure the DirectLOGIC CPUs (continued) DirectLOGIC MODBUS Port Configuration for DL05, D2-250(-1), or D4-450 The following configuration example is specific to the D2-250(-1) and DL05. Refer to the appropriate CPU User Manual for the specifics on your DirectLogic CPU. • In DirectSOFT, choose the PLC menu, then Setup, then “Secondary Comm Port”. • From the Port list box, choose “Port 2”. • For the Protocol, select ONLY “MODBUS”. (Do not select multiple protocols.) • In the Timeout list box, select “800 ms”. • Response Delay Time should be “0ms”. • The Station Number should be set to “1” to make the D2-250(-1) or DL05 CPU a MODBUS Master. • The Baud Rate should be set at “9600” (or higher, if using an FA-ISOCON network adapter module). • In the Stop Bits list box, choose “1”. • In the Parity list box, choose “Odd”. The DL250 network instructions used in Master mode will access only slaves 1 to 90. Each slave must have a unique number. 2nd Edition 07/06/2011 GS1 Series AC Drive User Manual 5–19