Execution via “Manual mode” window: The reference steps necessary for optimization can be executed in a user-friendly way via the „Manual mode“ window. The following settings are required for the manual mode window and the oscilloscope: Figure 35 Open control window Make settings: - Control mode = (SCON) Speed-controlled - Acceleration ramp = 0 Optimizing the speed controller Open scope: Setting: Channels: CH 0 = speed reference (nref) CH 1 = actual speed (nact) CH 2 = actual torque (mact) Trigger: Trigger signal: Speed reference (nref) Mode: Rising edge Level: 30 rpm Pretrigger: 0 % Time: Samplingtime: = base time (6.25E-0.5 s) Recording time = 0,2 s Figure 36 46 Setting the channels on the oscilloscope Harmonic Drive AG YukonDrive 1003374 01/2012