Transcript
Normal Condition : X = S (Amps) x ____ Hrs. (Backup time required) X=(50x10^-3)*48hrs = 2.4 Fire current (F) = Max. NAC Current =0.0833hr Alarm Condition : = 600mA @ 5 min [5/60] Y = F (Amps) x ____ Hrs. (Backup time required) Y=(600x10^-3)*0.0833hr(5min)=0.04998 Battery Ah required : AH = (X + Y) x 1.2 (Derating Factor). AH=(2.4 + 0.04998)*1.2 = 2.939 Note: Refer specification (Page 12) for Quiescent, standby, alarm currents Chapter 8: Trouble Shooting 46