6 Functional modules in the Fieldbus system
6.5 FBOUT-16
Output module with 16 outputs (binary)
P1
Connection from preceding
module
P2
Connection to the
next module
LED 0 - 15
Status display
-outputs-
LED 16 / green
Operating voltage
Outputs
Terminal 0 ...15
Fuse 8 A
(medium time-lag)
Operating voltage
Terminal 16
+ 24 V / DC / ± 20 %
0 V / DC / GND
Terminal 17
Notice!
Every output is fitted with protection against short circuit and excess temperature.
After a short circuit the control of the appropriate output must be reset. Only then
is the output ready for operation again.
Technical data
Outputs:
Maximum switching voltage:
Minimum switching voltage:
Constant load per output:
Total constant load of board:
Peak load per output:
6-6
30 V DC
19 V DC
1A
8A
3 A / 10 sec. / 45° C ambient temperature
ferrocontrol Steuerungssysteme