Download BC216 Manual Part B
Transcript
Chapter 4 • Connection 4.8.1.2 User Manual Series BC216 / Part B Connection of the fire brigade control unit FBF58-2, the key safe adapter AD800-1 and additional installations N T B 216-1 FB F 58-2 0 ,8 Af 5V 3 24V S i5 C urrent lim itation 4 0 ,8 Af 1,8 A 5 S i4 M ains PE 2 30V ~/50H z N 0,5 A t L P rim a ry sw itch contr. 44 1 F ire control activated 2 24V 6 7 560 24V 1) 10k 3 2,2k 24V 8 0 ,1 Af 11 S i3 S i1 5V 24V 560 12 E xtinguishing system activated 13 C ontrol logic ye gn 2) 14 10k 4 2,2k 5 20m A -Loop F W I2-1 6 7 8 1 00E 11 prim ary TD activated 24V A D 800-1 15 16 O perating voltage 1 10k 47k 17 F SS 80 0-1 22k 4) 47k 100 k 17 10k S abotage f. brig. ke y box 4) 12 19 21 Fa ult 100E 3) 1k 5,6k E xtinguishing syst. 47k 100 k 1k A larm 18 10k E xtin g.syst. activation A ctivation C onfirm ation 20 1 R ela y o utput 1 2 c prim ary TD activated I1 3 I2 D 24V C Ta Infra net T N A 10 Tb La T eleph one connection Lb 4 R ela y o utput 2 5 6 24V prim ary TD activated F lashlight 1)...The light-emitting diode "fire control activated" must be activated by the fire control. 2)...The light-emitting diode "extinguishing system activated" must be activated by the extinguishing system 3)...If burglar alarm and fault are jointly connected as "sabotage" to the fire brigade interface in the shown manner, the resistor 5.6kΩ on the printed circuit board of the AD800-1 must be removed (see manual AD800-1). 4)...The output "burglar alarm" is normally connected to a burglar alarm panel. The output "fault" of the AD800-1 can also be connected to a GIF8-1 as fault detector. If in this case the AD800-1 is not connected as the last "detector" of the fault detector zone, the resistor 5.6kΩ 3) must be removed. Figure 33: Connection of the fire brigade control unit FBF58-1, the key safe adapter AD800-1 and additional installations to the fire detection control panel Series BC216 HB216BE.SAM / 0140 / AN9161206 ZN5015/59/44