Creating Graphs Section 4-8 S Ref Table: Specify the number of the memory table to be referenced here. Pressing the [F1] (Lst Slct) key enables selection from a memory table list. S 100% Val S 0% Val S −100% Val: Specify the reference methods for 100%, 0%, and −100% values. If “Num Table” is specified, specify the numeral table number. If not using an NT30, NT30C, NT610G, or NT610C and Ver.2 or a later version of the direct connection function, only the “Fix Num” setting for the 100% value is valid. When “Num Table” is specified, pressing the [F1] (Lst Slct) key enables the memory table to be selected from a displayed list. S Display %: Specify whether or not a percentage value is displayed on the screen. S Details S Direction: Specify the orientation of the bar (up, down, right, left) here. S Frame: Specify whether or not a graph frame is displayed here. S Dsp Sign: Specify whether or not a minus sign is to be displayed in the case of negative values here. If “Yes” is specified, the center of the graph area is displayed at the origin to allow the display of negative values. S Color: Specify the display color of the bar graph when it shows positive values and the display color when it shows negative values (NT30C, NT610C only). S % Disp Det: Set the label display settings. Display smoothing cannot be specified with the NT20S, NT20M, NT600S, or NT600M. It is also not possible to specify a scale of x64 when using an NT20S or NT20M. S % Col Set: Specifies the character color and background color of the “%” character (NT30C, NT610C only). 119