Download User Manual - Delta Electronics
Transcript
Wiring 4.4.2. Digital Input & EPO Functions Communication Module provides 6 sets of digital input function(K1~K6) and 1 set of emergency power off function (EPO). When the outer external switch is short-circuited, the inverter will reduce power or shutdown immediately. Digital Input*6 EPO*1 RPI M6A/ M8A/ M10A Figure 4-8 EPO functions Pin Define Short Inverter’s action 1 K1 VCC & K1 No active power 2 K2 VCC & K2 Maximum 30% active power 3 K3 VCC & K3 Maximum 60% active power 4 K4 VCC & K4 Full active power 5 K5 VCC & K5 Reserved 6 K6 VCC & K6 Reserved 7 EPO VCC & EPO Emergency power off 8 VCC Table 4-6 Definition of digital input & EPO functions 21