Download Cover Page - NV Series
Transcript
Figure 5 Separated Combustion -Vertical Venting 6 ft. (1.8m) Min. to Wall or Adjoining Building Exhaust Vent Approved Vent Caps Combustion Air Inlet 2.5 ft. (0.75m) Min. 12 in. (0.3m) Min. 18 in. (0.46m) Min. * (See Note) Exhaust Tee with Drip Leg and Cleanout Cap 18 in. (0.46m) Min. Heating Appliance * Provide sufficient height to exceed expected snow depth Figure 6 Separated Combustion-Horizontal Venting 5 ft. (1.5m) Min. 25 ft. (15.2m) Max. Equivalent Length Building Overhang Pitch pipes down ¼ in./ ft. (21mm / m) Toward terminal caps to allow for Condensate drainage 3 ft. (0.9m) Min. 12 in. (0.3m) 6ft. (1.8m) Min. 24 in. (0.6m) 9 3 ft. (0.9m) Min. Above Grade Size by expected Snow depth Adjacent Building