24: REMOTE I/O SYSTEM Special Data Registers for INTERBUS Master Information Six data registers are assigned to store the system error and status information. Allocation No. Description INTERBUS Master System Error Information D8178 0 Normal 1 INTERBUS master DPRAM is Not Ready (DPRAM fault, etc.) 2 INTERBUS master is Not Ready (master unit fault, etc.) 3 No response from INTERBUS master (timeout error) 4 System error (unexpected reply from INTERBUS master) 5 Entry count error (disparity of quantity of nodes between actual system setup and Function Area Settings value) 6 Data size error (bus station of invalid size is connected) 7 ID code error (bus station of invalid type is connected) 8 Maximum node quantity over (more than 32 nodes are connected) Remarks Occurred process Initialization process or recovering process from Bus NG INTERBUS Master Status Transition Number D8179 24-10 0 Power ON 1 DPRAM and master ready (ready for receiving service command) 2 Reading and identification of configuration complete 3 I/O logical addressing complete 4 Set the bus active 5 Set the bus to run (I/O data updated) 6 Bus NG occurred 5 is stored during normal operation D8180 ****h INTERBUS Master Acknowledge Code Stores execution result of remote I/O master command request. D8181 ****h INTERBUS Master Additional Error Information Stores additional error information of D8180 D8182 ****h INTERBUS Master Error Code See page 24-16 D8183 ****h INTERBUS Master Error Location See page 24-16 OPENNET CONTROLLER USER’S MANUAL 0 (normal completion) or error code is stored