A082 DB Resistor Sel Range: 0 = Disabled 1 = Normal RA Resistor (5% Duty Cycle) 2 = No Protection (100% Duty Cycle) 3 to 99 = Duty Cycle Limited (3% to 99% Duty Cycle) Default: 0 = Disabled See also: P037 Enables/disables external dynamic braking. A083 S Curve % Range: 0 to 100% Default: 0% (Disabled) See also: N/A Sets the percentage of acceleration or deceleration time that is applied to the ramp as an S Curve. Time is added, 1/2 at the beginning and 1/2 at the end of the ramp. For example: If Accel Time = 10 seconds, and the S Curve % setting is 50%, the S Curve time will be 10 x 0.5 = 5 seconds. The total time will be 10 + 5 = 15 seconds. See figure 9.6 for an example. Accel Time = 10 sec S Curve% = 50% S Curve Time = 10 x 0.5 = 5 sec Total Time = 10 + 5 = 15 sec 50% S Curve Target Target/2 1/2 S Curve Time 2.5 Seconds Accel Time 10 Seconds 1/2 S Curve Time 2.5 Seconds Total Time to Accelerate = Accel Time + S Curve Time Figure 9.6 – S Curve % (A083) Example 9-22 MD65 AC Drive User Manual