T2000
Micro variable speed drives
VAT2000
Input voltage
Heavy duty / Constant torque (1)
overload 150% 60 sec.
Input
Output
Maximum (3)
power
current
motor power
kVA
A
kW
Light duty / Variable torque (2)
overload 120% 60 sec.
Input
Output
Maximum (3)
power
current
motor power
kVA
A
kW
Protection
degree
Cat. no.
Ref. no.
3ph
200V - 230V
1
1.7
2.7
3.8
5.5
8.3
11.4
15.9
21.1
26.3
31.8
41
50
3
5
8
11
16
24
33
46
61
76
92
118
144
0.4
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
1.2
2.1
3.0
5.1
7.6
10.0
14.5
19.3
24.2
29.7
37.4
45
55
5
8
11
16
22
33
42
61
76
86
108
134
161
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
IP20
IP20
IP20
IP20
IP20
IP20
IP20
IP20
IP20
IP00
IP00
IP00
IP00
U2KN00K4S
U2KN00K7S
U2KN01K5S
U2KN02K2S
U2KN04K0S
U2KN05K5S
U2KN07K5S
U2KN11K0S
U2KN15K0S
U2KN18K5S
U2KN22K0S
U2KN30K0S
U2KN37K0S
168000
168001
168002
168003
168004
168005
168006
168007
168008
168009
168010
168011
168052
3ph
380V - 460V
1
1.7
2.5
3.8
5.9
9
11.7
15.9
21.4
25.6
30.4
41.5
50
60
75
100
120
150
170
220
300
350
400
1.5
2.5
3.6
5.5
8.6
13
17
23
31
37
44
60
72
87
108
145
173
214
245
321
428
519
590
0.4
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
315
1.7
2.5
3.8
5.9
9.0
11.7
15.9
21.4
25.6
30.4
41.5
50.5
55
75
100
120
140
170
200
250
330
400
450
2.5
3.6
5.5
8.6
13
17
23
31
37
44
60
73
84
108
147
179
208
242
293
365
479
581
651
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
315
370
IP20
IP20
IP20
IP20
IP20
IP20
IP20
IP20
IP20
IP20
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
U2KX00K4S
U2KX00K7S
U2KX01K5S
U2KX02K2S
U2KX04K0S
U2KX05K5S
U2KX07K5S
U2KX11K0S
U2KX15K0S
U2KX18K5S
U2KX22K0S
U2KX30K0S
U2KX37K0S
U2KX45K0S
U2KX55K0S
U2KX75K0S
U2KX90K0S
U2KX110KS
U2KX132KS
U2KX160KS
U2KX200KS
U2KX250KS
U2KX315KS
168024
168025
168026
168027
168028
168029
168030
168031
168032
168033
168034
168035
168036
168037
168038
168039
168040
168041
168042
168043
168044
168045
168046
3ph
400V
1
1.7
2.5
3.8
5.9
9
11.7
15.9
21.4
25.6
30.4
41.5
50
60
-
1.5
2.5
3.6
5.5
8.6
13
17
23
31
37
44
60
72
87
-
0.4
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
-
1.7
2.5
3.8
5.9
9.0
11.7
15.9
21.4
25.6
30.4
41.5
50.5
55
75
2.5
3.6
5.5
8.6
13
17
23
31
37
44
60
73
84
108
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
55
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
IP54
U2KX00K4SP54B
U2KX00K7SP54B
U2KX01K5SP54B
U2KX02K2SP54B
U2KX04K0SP54B
U2KX05K5SP54B
U2KX07K5SP54B
U2KX11K0SP54B
U2KX15K0SP54B
U2KX18K5SP54B
U2KX22K0SP54B
U2KX30K0SP54B
U2KX37K0SP54C
U2KX37K0SP54V
U2KX45K0SP54C
U2KX45K0SP54V
169471
169472
169473
169474
169475
169476
169477
169478
169479
169480
169481
169482
169483
169484
169485
169486
(1) Heavy duty / Constant torque ratings
- Ambient temperature -10ºC to 50ºC for all range (IP54 range up to 40ºC)
- Drives up to U2KN22K0S or up to U2KX30K0S allow specified current ratings when carrier frequency is set up to 10KHz.
Above 10KHz, derate output current by 7% per 1KHz.
- Drives above U2KN22K0S or U2KX37K0S and above allow specified current ratings when carrier frequency is set up to 4KHz.
Above 4KHz, derate output current by 7% per 1KHz
J
(2) Light duty / Variable torque ratings
- Ambient temperature -10ºC to 50ºC (IP54 up to 40ºC). Fro drives up to U2KN7K5S derate output current by 2% per 1ºC if ambient temperature exceeds 40ºC
- Maximum recommended carrier frequency is 4KHz. Higher carrier frequency is allowed if drive’s output current is derated according following expression:
VT - CT
Amps, per 1KHz
6
VT = Drive rated current in variable torque
CT = Drive rated current in constant torque
- Ratings are given for standard four poles motors. Otherwise, check motor nameplate
Remark: More information is given in Product Manual
(3) Ratings given are for standard 4 poles induction motors
VAT2000
DC supply
drives for common bus operation
We can supply VAT2000 drives for common bus operation DC supply 270-360VDC or 520-720VDC.
Please ask your dealer for more information.
J.10
GE Power Controls