Telepace C Tools Function Specifications hartCommand11 Read Unique Identifier Associated with Tag Syntax #include <ctools.h> BOOLEAN hartCommand11(unsigned module, char * deviceTag, HART_DEVICE * device); Description This function reads the unique identifier of a HART device using command 11. This is a link initialization function. The function has three parameters: the module number of the 5904 module (0 to 3); a pointer to a null terminated string containing the tag of the HART device; and a pointer to a HART_DEVICE structure. The information read by command 11 is written into the HART_DEVICE structure when the response is received by the 5904 interface. The function returns TRUE if the command was sent. The function returns FALSE if the module number is invalid. Notes The function returns immediately after the command is sent. The calling program needs to wait for the response to be received. Use the hartStatus command to read the status of the command. The number of attempts and the number of preambles sent are set with the hartSetConfiguration command. A program needs to initialize the link before executing any other commands. See Also hartCommand0, hartStatus, hartSetConfiguration Document (Version 2.50) 5/12/2011 260