ioLogik E2262 User’s Manual
First Edition, May 2008
www.moxa.com/product
© 2008 Moxa Inc., all rights reserved.
Reproduction without permission is prohibited.
ioLogik E2262 User’s Manual
The software described in this manual is furnished under a license agreement, and may be used only in
accordance with the terms of that agreement.
Copyright Notice
Copyright © 2008 Moxa Inc.
All rights reserved.
Reproduction without permission is prohibited.
Trademarks
MOXA is a registered trademark of Moxa Inc.
All other trademarks or registered marks in this manual belong to their respective manufacturers.
Disclaimer
Information in this document is subject to change without notice, and does not represent a commitment on the
part of Moxa.
Moxa provides this document “as is,” without warranty of any kind, either expressed or implied, including, but
not limited to, its particular purpose. Moxa reserves the right to make improvements, and/or changes to this
manual, or to the products, and/or the programs described in this manual, at any time.
Information provided in this manual is intended to be accurate, and reliable. However, Moxa assumes no
responsibility for its use, or for any infringements on the rights of third parties that may result from its use.
This manual might include unintentional technical or typographical errors. Changes are made periodically to the
information herein to correct such errors, and these changes are incorporated into new editions of the manual.
Technical Support Contact Information
www.moxa.com/support
Moxa Americas:
Toll-free: 1-888-669-2872
Tel: +1-714-528-6777
Fax: +1-714-528-6778
Moxa Europe:
Tel: +49-89-3 70 03 99-0
Fax: +49-89-3 70 03 99-99
Moxa Asia-Pacific:
Tel: +886-2-8919-1230
Fax: +886-2-8919-1231
Moxa China (Beijing office):
Tel: +86-10-6872-3959/60/61
Fax: +86-10-6872-3958
Table of Contents
Chapter 1
Introduction ...............................................................................................1-1
Overview .............................................................................................................................. 1-2
Traditional Remote I/O................................................................................................. 1-2
Active Ethernet I/O....................................................................................................... 1-2
Click&Go ..................................................................................................................... 1-2
Optional Liquid Crystal Display Module (LCM) ......................................................... 1-3
Product Features ................................................................................................................... 1-3
Packing List.......................................................................................................................... 1-3
Product Specifications .......................................................................................................... 1-4
Physical Dimensions ............................................................................................................ 1-6
With LCD Module........................................................................................................ 1-6
Without LCD Module................................................................................................... 1-7
Hardware Reference ............................................................................................................. 1-7
Panel Guide .................................................................................................................. 1-7
LED Indicators ............................................................................................................. 1-8
Chapter 2
Initial Setup ................................................................................................2-1
Hardware Installation ........................................................................................................... 2-2
Connecting the Power................................................................................................... 2-2
Grounding the ioLogik E2262 ...................................................................................... 2-2
Connecting to the Network........................................................................................... 2-2
Setting the RS-485 Baudrate ........................................................................................ 2-2
Adding More I/O Channels .......................................................................................... 2-3
Software Installation............................................................................................................. 2-3
Chapter 3
Utilities .......................................................................................................3-1
Introduction to ioAdmin ....................................................................................................... 3-2
Features of ioAdmin ............................................................................................................. 3-2
ioAdmin Main Screen........................................................................................................... 3-4
Main Screen Overview ................................................................................................. 3-4
Wiring Guide ................................................................................................................ 3-5
Menu Items........................................................................................................................... 3-5
File................................................................................................................................ 3-5
System .......................................................................................................................... 3-6
Sort ............................................................................................................................... 3-7
Help .............................................................................................................................. 3-7
Quick Links .................................................................................................................. 3-7
Main Window ....................................................................................................................... 3-8
I/O Configuration Tab (General) .................................................................................. 3-8
Server Info Tab............................................................................................................. 3-8
Server Settings Tab (General) ...................................................................................... 3-9
Message Monitor Tab ................................................................................................... 3-9
ioAdmin Administrator Functions ...................................................................................... 3-10
I/O Configuration Tab (Administrator) ...................................................................... 3-10
Server Settings Tab (Administrator)........................................................................... 3-14
Network Tab ............................................................................................................... 3-15
Firmware Update Tab................................................................................................. 3-16
Watchdog Tab............................................................................................................. 3-17
Click&Go Logic Tab .................................................................................................. 3-17
Server Context Menu.................................................................................................. 3-18
Using TFTP to Import/Export Configuration ..................................................................... 3-21
Using ioEventLog............................................................................................................... 3-22
Installing ioEventLog ................................................................................................. 3-22
Basic Functions........................................................................................................... 3-22
Configuration.............................................................................................................. 3-23
Checking Connected Devices ..................................................................................... 3-24
Opening Log Files ...................................................................................................... 3-24
Clearing the Log ......................................................................................................... 3-24
Chapter 4
Using the Web Console ............................................................................4-1
Introduction to the Web Console .......................................................................................... 4-2
Basic Settings ....................................................................................................................... 4-2
Network Settings .................................................................................................................. 4-3
General Settings............................................................................................................ 4-3
Ethernet Configuration ................................................................................................. 4-3
RS-485 Settings ............................................................................................................ 4-4
I/O Settings........................................................................................................................... 4-4
TC Channels ................................................................................................................. 4-4
DO Channels ................................................................................................................ 4-6
System Management ............................................................................................................ 4-7
Accessible IP Settings................................................................................................... 4-7
SNMP Agent ................................................................................................................ 4-8
Network Connection..................................................................................................... 4-8
Firmware Update .......................................................................................................... 4-8
Import System Config .................................................................................................. 4-9
Export System Config .................................................................................................. 4-9
LCM ..................................................................................................................................... 4-9
Change Password................................................................................................................ 4-10
Load Factory Default.......................................................................................................... 4-10
Save/Restart........................................................................................................................ 4-10
Chapter 5
Click&Go Logic..........................................................................................5-1
Overview .............................................................................................................................. 5-2
Features ................................................................................................................................ 5-2
Click&Go Logic Basics........................................................................................................ 5-2
Working with Rules...................................................................................................... 5-3
Defining Logic Rules ........................................................................................................... 5-4
Summary of IF/THEN Parameters ............................................................................... 5-4
IF Conditions ................................................................................................................ 5-4
THEN Actions .............................................................................................................. 5-4
Active Message............................................................................................................. 5-5
SNMP Trap................................................................................................................... 5-6
E-mail ........................................................................................................................... 5-7
Working with Click&Go Rulesets ........................................................................................ 5-8
Activating the Ruleset................................................................................................... 5-8
Ruleset Management Bar.............................................................................................. 5-8
Ruleset Import/Export .................................................................................................. 5-8
Appendix A
Liquid Crystal Display Module (LCM) ..................................................... A-1
Appendix B
Modbus Mappings.................................................................................... B-1
0xxxx Read/Write Coils (Functions 1, 5, 15) .......................................................................B-1
3xxxx Read Only Registers (Function 4) .............................................................................B-3
4xxxx Read/Write Registers (Functions 3, 6, 16).................................................................B-5
5xxxx Write Registers (Function 8)......................................................................................B-9
Appendix C
Used Network Port Numbers................................................................... C-1
Appendix D
SNMP MIB II .............................................................................................. D-1
RFC1213 MIB II Supported SNMP Variables..................................................................... D-1
Appendix E
Factory Default Settings .......................................................................... E-1
Appendix F
Pinouts and Cable Wiring.........................................................................F-1
Ethernet Port Pinouts ............................................................................................................ F-1
Serial Port Pinouts ................................................................................................................ F-1
Thermocouple Input Wiring ................................................................................................. F-1
Structure ....................................................................................................................... F-1
2-wire............................................................................................................................ F-2
Digital Output....................................................................................................................... F-2
Structure ....................................................................................................................... F-2
Output Channel............................................................................................................. F-2
Terminal Block Pin Assignments.......................................................................................... F-3
1
Chapter 1
Introduction
The ioLogik E2262 is a stand-alone Active Ethernet I/O server. It connects thermocouple sensors
and digital output on/off switches for automation applications over Ethernet and IP-based
networks.
The following topics are covered in this chapter:
‰ Overview
¾ Traditional Remote I/O
¾ Active Ethernet I/O
¾ Click&Go
¾ Optional Liquid Crystal Display Module (LCM)
‰ Product Features
‰ Packing List
‰ Product Specifications
‰ Physical Dimensions
¾ With LCD Module
¾ Without LCD Module
‰ Hardware Reference
¾ Panel Guide
¾ LED Indicators
ioLogik E2262 User’s Manual
Introduction
Overview
(shown with and without optional LCM)
The ioLogik E2262 is part of the E2000 line of ioLogik Active Ethernet I/O servers, which are
designed for intelligent, pro-active status reporting of attached thermocouples over a network. It
includes 2 MB of Flash ROM and 8 MB of SDRAM. An optional hot-pluggable Liquid Crystal
Display Module (LCM) can be used to view and configure device settings.
Traditional Remote I/O
Ethernet remote I/O solutions have been on the market for a long time. Traditional solutions are
“passive,” in the sense that I/O servers wait passively to be polled by a host computer. The
response time in this type of setup, however, tends to be on the order of seconds. The “passive”
remote I/O structure is simply inadequate for data acquisition and control systems that require a
response time on the order of hundredths of seconds.
Active Ethernet I/O
Moxa’s Active Ethernet I/O line was developed specifically to address the limitations of the
traditional passive approach. Rather than having the host computer poll the I/O device server over
the network for the status of each I/O device, the Active Ethernet I/O server intelligently sends the
host computer status information under user-specified conditions. This is a report by exception
approach, which greatly reduces the load on CPU and network resources. Network packets are far
fewer in number and far smaller in size, since I/O information is only sent when necessary, and
only information from the specified I/O device is sent. Based on field tests of an ioLogik E2000
series server used in an RFID system, 50 ms is the typical response time over a 100 Mbps Ethernet
network. Moxa’s active I/O messaging system uses TCP or UDP for I/O messaging and supports
sending messages to up to ten host computers simultaneously.
In addition to providing intelligent status reporting, Active Ethernet I/O servers are backwards
compatible, with all of the functions and capabilities of traditional passive remote I/O servers.
Click&Go
Moxa developed the Click&Go Logic control interface for easy configuration and deployment of
Active Ethernet I/O. Click&Go’s intuitive, graphical interface lets administrators use simple
IF/THEN statements as rules to determine how the Active Ethernet I/O server responds to different
I/O conditions. For example, the Active Ethernet I/O server could be programmed so that if the
temperature recorded by an attached sensor reaches a certain value, an attached switch is turned on
and an e-mail is sent to an administrator. Click&Go makes it easy to define a set of these rules,
which will become the basis for your Active Ethernet I/O system.
1-2
ioLogik E2262 User’s Manual
Introduction
Optional Liquid Crystal Display Module (LCM)
In order to make user easy view, the ioLogik E2262 supports an optional hot-pluggable Liquid
Crystal Display Module (LCM) for field management and configuration. The LCM can display
network and I/O settings such as temperature value. The ioLogik E2262’s IP address and netmask
can also be configured using the LCM, and one LCM can be used to maintain and configure all
ioLogik 2000 devices.
Product Features
y Click&Go Logic for easy configuration of your Active Ethernet I/O system
y High-speed active I/O messaging
y 8 input channels for various thermocouple temperature sensors, such as J, K, T, E, R, S, B, and
N type TC sensors, and more, with software selectable filtering time
y 4 channels for 24 VDC output with Pulse Output mode and software selectable pulse width
y 10/100 Mbps Ethernet supporting Modbus/TCP and up to 10 hosts
y Windows utility and quick programming library for VB, VC++, BCB (coming soon)
y Expandable I/O through optional RS-485 modules
y Supports SCADA software including InTouch, Citect, and iFix32
y SNMP for system management and I/O status
y Remote management over the network including firmware updates
y Supports TFTP server to import configuration
y Power-on and safe status settings for digital output
y Optional hot-pluggable LCM for status display and configuration
Packing List
The ioLogik E2262 is shipped with the following items:
Standard Accessories
y ioLogik E2262 Active Ethernet I/O server
y Document and Software CD
Optional Accessories
y LDP1602 ioLogik liquid crystal display module (LCM)
NOTE: Notify your sales representative if any of the above items are missing or damaged.
1-3
ioLogik E2262 User’s Manual
Introduction
Product Specifications
LAN
Ethernet
Protocols
10/100 Mbps, RJ45
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP
(MIB for I/O and Network), HTTP
Serial
Interface
Serial Line Protection
RS-485 (2-wire): Data+, Data-, GND
15 KV ESD for all signals
Serial Communication Parameters
Parity
Data Bits
Stop Bits
Flow Control
Speed
Protocol
Built-in RTC
None
8
1
None
1200 to 115200 bps
Modbus/RTU
Yes
Thermocouple Input
Channels
I/O Mode
Input Impedance
Resolution
TC Conversion Rate
Accuracy
Zero Drift
Span Drift
CMR @50/60Hz
NMR @50/60Hz
Optical Isolation
Supported Thermocouple Types
8, thermocouple sensors
J, K, T, E, R, S, B, and N type TC sensors, and mV
> 1 mega-ohm
0.1°C
90 ms per channel
+/-0.1%
+/- 6 uV/ºC (typical)
+/- 25 ppm/ºC
92 dB
92 dB
2 KVrms / 3 KVDC
Sensor Type
J
K
T
E
R
S
B
N
Degree Range
0 to 750°C
-200 to 1250°C
-200 to 350°C
-200 to 900°C
-50 to 1600°C
-50 to 1760°C
600 to 1700°C
-200 to 1300°C
Count Range
0 to 7500
-2000 to 12500
-2000 to 3500
-2000 to 9000
-500 to 16000
-500 to 17600
6000 to 17000
-2000 to 13000
Supported millivolt Resolution
Mode
2.3 µV
1.15 µV
0.5 µV
-78.126 to +78.126 mV
-39.062 to +39.062 mV
-19.532 to +19.532 mV
-781260 to 781260
-390620 to 390620
-195320 to 195320
Virtual Thermocouple
Channels
Operation Mode
8
Average, Difference
Digital Output
Channels
On-state Voltage
Output Current Rating
Optical Isolation
4, sink type
24 VDC nominal, 30 VDC max.
Max. 200 mA per channel
2 KVrms/3 KVDC
1-4
ioLogik E2262 User’s Manual
Protection
Introduction
Over temperature shutdown: 170°C
Over current limit: 750 mA/channel (typical)
Power Requirements
Power Input
Power Consumption
Field Power
24 VDC nominal, 12 to 48 VDC (max.)
175 mA @ 24 VDC (typical)
4.6 W with LCM (max.)
24 VDC nominal, up to 48 VDC
Mechanical Specifications
Wiring
I/O cable max. 14 AWG
Environmental
Operating Temperature
Storage Temperature
Shock
Freefall
Vibration
MTBF
-10 to 60ºC (14 to 140ºF), 5 to 95%RH
-40 to 85ºC (-4 to 185ºF), 5 to 95%RH
IEC60068-2-27
IEC60068-2-32
IEC60068-2-6
> 200,000 hrs @ 25°C
Agency Approvals
EMC
Safety
FCC Part 15, CISPR (EN55022) Class A
CE-IEC61000-4-2 (ESD), Level 2/3
CE-IEC61000-4-3 (RS), Level 2
CE-IEC61000-4-4 (EFT), Level 2
CE-IEC61000-4-5 (Surge), Level 3
CE-IEC61000-4-6 (CS), Level 2
CE-IEC61000-4-8 (PM), Level 1
CE-IEC61000-4-11 (Dip)
CE-EN61000-6-2
CE-EN61000-6-4
UL 508
Warranty
Period
2 years
1-5
ioLogik E2262 User’s Manual
Introduction
Physical Dimensions
With LCD Module
5.95
Unit = mm
39.5
79
9.5
93.02
115
121.8
10.98
46.51
44.5
3.4
79
3.39
35.1
6
6.89
10.7
5.95
9.51
45.63
57.5
1-6
ioLogik E2262 User’s Manual
Introduction
Without LCD Module
Unit = mm
5.95
9.5
79
39.5
10.7
24.44
9.51
45.39
10.98
93.02
115
121.8
46.51
6
Hardware Reference
Panel Guide
(TB1)
(TB2)
NOTE: The reset button restarts the server and resets all settings to factory defaults. Use a pointed
object such as a straightened paper clip to hold the reset button down for 15 sec. The RDY LED
will turn red as you are holding the reset button down. The factory defaults will be loaded once the
RDY LED turns green again. At this point, you can release the reset button.
1-7
ioLogik E2262 User’s Manual
Introduction
LED Indicators
Ethernet
Ethernet
orange
green
(flashing)
Valid 10 Mbps Ethernet connection
Valid 100 Mbps Ethernet connection
Transmitting or receiving data
System
PWR
RDY
Serial
Thermocouple
TC × 8
channels
Digital Output
DO × 4
channels
DO PWR
red
off
red
green (steady)
green (flashing)
green & red (flashing)
off
(flashing)
Power is on
Power is off
System error
Unit is functioning normally
Click&Go ruleset is active
Safe status settings activated
Power is off or there is a power problem.
Serial port is receiving/transmitting data
green
red
off
Normal operation
Channel error or no connection
Channel off
green
off
red
off
ON status
OFF status
ON status
No power in
1-8
2
Chapter 2
This chapter describes how to install the ioLogik E2262.
The following topics are covered:
‰ Hardware Installation
¾ Connecting the Power
¾ Grounding the ioLogik E2262
¾ Connecting to the Network
¾ Setting the RS-485 Baudrate
¾ Adding More I/O Channels
‰ Software Installation
Initial Setup
ioLogik E2262 User’s Manual
Initial Setup
Hardware Installation
Connecting the Power
Connect the 12 to 48 VDC power line to the ioLogik E2262’s terminal block (TB1). If power is
properly supplied, the Power LED will glow a solid red color until the system is ready
ATTENTION
Disconnect the power before installing and wiring
Disconnect the power cord before installing and/or wiring your ioLogik E2262.
Do not exceed the maximum current for the wiring
Determine the maximum possible current for each power wire and common wire. Observe all
electrical codes dictating the maximum current allowable for each wire size.
If the current exceeds the maximum rating, the wiring could overheat, causing serious damage to
your equipment.
Grounding the ioLogik E2262
There are two grounding points on the ioLogik E2262: the wall mounting point and the DIN-rail
mounting plate. Note that both grounding points are actually connected to the same conducting
pathway.
Connecting to the Network
1. Connect the ioLogik E2262 to the host PC with an Ethernet cable. For initial setup of the
ioLogik E2262, it is recommended that the ioLogik E2262 be configured using a direct
connection to a host computer rather than remotely over the network.
2. Note the ioLogik’s default IP settings:
Netmask
Gateway
IP Address
192.168.127.254
255.255.255.0
None
Configure the host PC’s IP address to 192.168.127.xxx. (xxx: from 001 to 253) so the ioLogik
will be visible on the network. In Windows, you will need to do this through the Control Panel.
3. Use ioAdmin or the web console to detect the ioLogik E2262. Once the ioLogik E2262 has been
detected, modify the settings as needed for your network environment, then restart the ioLogik
E2262. For information on ioAdmin, please refer to Software Installation later in this chapter.
Setting the RS-485 Baudrate
The RS-485 port on the ioLogik E2262 is reserved for connecting to another ioLogik R2000 I/O
server. The RS-485 port can run Modbus/RTU or I/O command sets. The baudrate is set by a
physical dial on the back of the ioLogik E2262. The default settings are baudrate = 115200, parity
check = N, data bits = 8, and stop bit = 1.
Baudrate for RS-485
(parameters are N, 8, 1)
Dial setting and corresponding baudrate:
0:115200 1:57600
2:38400
3:19200
4:9600
5:4800
6:2400
7:1200
Remember to restart the ioLogik E2262 after making any changes to the RS-485 baudrate.
2-2
ioLogik E2262 User’s Manual
Initial Setup
Adding More I/O Channels
A cost effective way to add more I/O channels to your ioLogik E2000 I/O server is to attach the
appropriate ioLogik R2000 I/O server. The two servers can be snapped together using the RS-485
system bus connector, as shown in the following figure. Digital I/O channels can be added using
the ioLogik R2110, and analog I/O channels can be added using the ioLogik R2140. For additional
details, please refer to the ioLogik R2110 or R2140 user’s manual.
Software Installation
ioAdmin is a Windows utility provided for the configuration and management of the ioLogik
E2262 and attached I/O devices. It can be used from anywhere on the network to monitor and
configure the ioLogik E2262. You can also configure some of the settings through the web console
or optional LCM.
1. Installation from CD: Insert the Document and Software CD into the host computer. In the root
directory of the CD, locate and run SETUP.EXE. The installation program will guide you
through the installation process and install the ioAdmin utility. You can also install the MXIO
DLL library or ioEventLog separately.
2. Open ioAdmin: After installation is finished, run ioAdmin from Start Æ Program Files Æ
MoxaÆ IO Server Æ Utility Æ ioAdmin.
3. Search the network for the server: When ioAdmin is started, a pop-up window will appear to
help you search for these I/O devices. Or, you can search for a specific model. On the menu bar,
select System ÆAuto Scan Active Ethernet I/O Server. In the dialog window that appears,
click Start Search to begin searching for the ioLogik E2262.
2-3
ioLogik E2262 User’s Manual
Initial Setup
If ioAdmin is unable to find the ioLogik E2262, there may be a problem with your network
settings.
When multiple ioLogik E2000 units are on the same network, remember that each unit has
the same default IP address. You will need to assign a different IP address to each unit to
avoid IP conflicts. ioAdmin automatically detects IP conflicts and gives you a chance to
modify each unit’s IP address in the “IP Address” columns. Click the “Set” button to reboot
the corresponding unit with its new IP address. Click the “Re-Search” button to refresh the
list of units found by ioAdmin.
2-4
ioLogik E2262 User’s Manual
Initial Setup
4. Monitoring I/O status: Once the ioLogik E2262 is found by ioAdmin, you can view the status
of all I/O devices on ioAdmin’s main screen.
You can now use ioAdmin to set up or configure your ioLogik E2262.
2-5
3
Chapter 3
Utilities
This chapter goes over the functions available in ioAdmin, the ioLogik E2262’s main
configuration and management utility.
The following topics are covered:
‰ Introduction to ioAdmin
‰ Features of ioAdmin
‰ ioAdmin Main Screen
¾ Main Screen Overview
¾ Wiring Guide
‰ Menu Items
¾ File
¾ System
¾ Sort
¾ Help
¾ Quick Links
‰ Main Window
¾ I/O Configuration Tab (General)
¾ Server Info Tab
¾ Server Settings Tab (General)
¾ Message Monitor Tab
‰ ioAdmin Administrator Functions
¾ I/O Configuration Tab (Administrator)
¾ Server Settings Tab (Administrator)
¾ Network Tab
¾ Firmware Update Tab
¾ Watchdog Tab
¾ Click&Go Logic Tab
‰ Server Context Menu
‰ Using TFTP to Import/Export Configuration
‰ Using ioEventLog
ioLogik E2262 User’s Manual
Utilities
Introduction to ioAdmin
The ioLogik I/O server can be managed and configured over the Ethernet by ioAdmin, a Windows
utility provided with your ioLogik E2262. ioAdmin’s graphical user interface gives you easy
access to all status information and settings.
The ioLogik E2262 also supports configuration by web console and by optional LCM, but full
configuration and management is only available through ioAdmin.
A new feature in ioAdmin automatically detects IP conflicts between ioLogik E2000 units. If
ioAdmin detects an IP conflict, a window will appear that allows you to resolve the IP conflict
immediately and restart each unit.
ioAdmin also includes Click&Go Logic control for the configuration of your Active Ethernet I/O
system.
ioAdmin consists of following software:
y ioAdmin with Click&Go Logic
y ioLogik 2000 Wiring Guide
y ioLogik 4000 Wiring Guide
Features of ioAdmin
Remote Management
Over the Ethernet network, ioAdmin allows
users to
z
z
z
z
Find and configure multiple ioLogiks
Monitor and configure attached I/O devices
Test I/O devices
Reset the ioLogik
On-line Wiring Guide
An on-line wiring guide can be opened from
within ioAdmin for your convenience. The easily
accessible wiring guide can save administrators
much time while planning or troubleshooting.
3-2
ioLogik E2262 User’s Manual
Utilities
Configuration File
ioAdmin allows the entire configuration of the
ioLogik E2262 to be saved as a file. The file is
viewable as text and can serve three purposes:
z
z
z
as a record or backup of configuration
as a template for the configuration of other
servers
as a quick reference guide for you to configure
Modbus drivers in a SCADA system
The file includes the following information:
1.
2.
3.
File name, date, and time
Model information
Modbus addresses
Server Management List
ioAdmin can import and export a list of
ioLogiks that are being managed. This file
can make it easier to manage all devices on
the network, and includes the following
information:
1.
2.
3.
4.
Server Name
Module Type
IP Address
Unit ID
3-3
ioLogik E2262 User’s Manual
Utilities
ioAdmin Main Screen
Main Screen Overview
This is ioAdmin’s main screen. The main window defaults to the I/O Configuration tab, which
displays a figure of the ioLogik E2262 and the status of every I/O channel below it. The other tabs
in the main window take you to server and network settings, and further functions are available
when you log on as an administrator. Note that configuration options are not available until you
log on as an administrator.
1
3
2
4
5
6
7
ioAdmin Main Screen
1. Title
2. Menu bar
3. Quick link
4. Navigation panel
5. Main window
6. Sync. rate status
7. Status bar
3-4
ioLogik E2262 User’s Manual
Utilities
Wiring Guide
ioAdmin provides a wiring guide to the ioLogik E2262. You can access the wiring guide by
right-clicking the figure of the ioLogik E2262 in the I/O Configuration tab. Select “Wiring Guide”
in the submenu to open a help file showing the wiring information and electrical characteristics of
the ioLogik E2262.
Menu Items
File
From the File menu, you can export the list of I/O servers that are currently displayed in the
navigation panel. You also can import a list of I/O servers into ioAdmin.
When importing a server list, you will be prompted to select which servers on the list need to be
imported.
3-5
ioLogik E2262 User’s Manual
Utilities
The file will have a .SLT extension and can be opened as a text file. The server list will provide
the following information for server:
1.
Server Name
2.
Module Type
3.
IP Address
4.
Unit ID
System
Several operations are possible from the System menu.
Auto Scan Active Ethernet I/O Server will search for ioLogiks on the network. When
connecting for the first time or recovering from a network disconnection, you can use this
command to find I/O servers that are on the network.
Network Interface allows you to select a network to use, if the PC has multiple network adapters
installed.
I/O Status Refresh Rate is used to adjust how often the I/O server is polled for device status. The
current rate is displayed on the status bar at the bottom of the window. Note that higher sync rates
result in higher loads on the network.
TCP Socket Timeout Interval allows you to select the preferred timeout value for TCP socket
communication.
COM Port Setting is used to set the parameters for Modbus communciation, such as baudrate,
data bits, and timeout interval. For most applications, this will involve connecting to ioLogik
R-Series devices.
Active Message Listen Port specifies the port number to use for Active Ethernet I/O messages. If
your network uses a firewall, you can coordinate this setting with your firewall settings to ensure
that active messages get through.
Reset NA4010 Network Adapter IP is used to re-assign an IP address to the NA-4010 network
adapter, for ioLogik 4000 systems.
3-6
ioLogik E2262 User’s Manual
Utilities
Sort
The Sort menu allows the server list in the navigation panel to be sorted by connection, type, and
location.
Help
In the Help menu, you can view wiring guides and information about ioAdmin.
Quick Links
Quick links are provided to search for I/O servers on the network and sort the server list.
Search network for I/O servers
Sort by connection
Sort by I/O server type
Sort by location
3-7
ioLogik E2262 User’s Manual
Utilities
Main Window
I/O Configuration Tab (General)
The I/O Configuration tab shows the status of every I/O channel. This is the default tab when you
first open ioAdmin.
Server Info Tab
Server information, such as firmware revision, is displayed in the Server Info tab.
3-8
ioLogik E2262 User’s Manual
Utilities
Server Settings Tab (General)
The Server Settings tab is where you log in as an administrator. This is required in order to gain
access to the ioLogik E2262 configuration options. If no administrator password has been set up,
simply click Login and leave the Password for entry field blank. Please refer to the ioAdmin
Administrator Functions section later on in this chapter for more detail.
Message Monitor Tab
The Message Monitor tab will display any TCP/UDP I/O messages received from the ioLogik
E2262. When you install the ioLogik E2262 for the first time, the Click&Go ruleset will not have
been defined yet, so no messages will be displayed. Please refer to Chapter 5 for information on
using Click&Go. Once a ruleset has been ddefined and activated, any TCP/UDP messages sent
from the ioLogik E2262 will be displayed in the Message Monitor tab.
Messages can be displayed in ASCII or in HEX. To display messages in HEX, make sure that
“Toggle HEX” is checked.
3-9
ioLogik E2262 User’s Manual
Utilities
ioAdmin Administrator Functions
For full access to all configuration options, log in as an administrator in the Server Settings tab.
This is required whenever you start up ioAdmin or boot up/restart the ioLogik E2262. When you
install the ioLogik E2262 for the first time, the password will be blank and you can simply click
Login. Additional functions will available after logging in, including the following new tabs:
When making configuration changes, you will need to click Update or Apply to save the changes.
Some changes will require a restart of the ioLogik E2262 in order to take effect, and you will be
given the option to restart the computer if necessary.
ATTENTION
You MUST log in to access any administrator function, including Network, Communication
Watchdog Timer, and Firmware Update tabs. If you forget the password, you can hold down the
ioLogik’s reset button to clear the password and load factory defaults. This will result in the loss
of all configuration settings and your Click&Go Logic ruleset!
I/O Configuration Tab (Administrator)
When logged on as an administrator, you can double click on a channel in the I/O Configuration
tab to configure that channel’s settings. A window will open with configuration options for that
channel. Settings made in this window can be copied to all I/O channels using the “Apply to all
channels” option. Options for Power on Settings and Safe Status Settings are also available.
Configuring Thermocouple Input Channels
The ioLogik E2262 provides 8 fixed physical TC input (Thermocouple) channels, each supporting
up to 8 different types including J, K, T, E, R, S, B, N types, and mV voltage inputs. The TC
channels are numbered from channel 0 to channel 7. Moreover, channel 8 to channel 15 are virtual
temperature channels that report a running average or difference of selected TC channels.
3-10
ioLogik E2262 User’s Manual
Utilities
The following table is a list of supported sensor types and ranges.
Type
Temperature Range
J
Count Range
0ºC to 750ºC
0 to
7,500
K
-200ºC to 1250ºC
-2,000 to 12,500
T
-200ºC to 350ºC
-2,000 to
3,500
E
-200ºC to 900ºC
-2,000 to
9,000
R
-50ºC to 1600ºC
-500 to 16,000
S
-50ºC to 1760ºC
-500 to 17,600
B
600ºC to 1700ºC
6,000 to 17,000
N
-200ºC to 1300ºC
-2,000 to 13,000
2.3 μV
- 78.126mV to + 78.126mV
-781,260 to 781,260
1.15 μV
- 39.062mV to + 39.062mV
-390,620 to 390,620
0.5 μV
- 19.532mV to + 19.532mV
-195,320 to 195,320
The status of attached sensors will be reported by the count value, which corresponds to the sensor
ranges shown above. For example, for a K type TC sensor, a count value of 10 corresponds to a
0.1°C reading. Moxa can only guarantee accuracy within the ranges shown above. Be sure to
verify the sensor type. Accurate readings beyond these ranges cannot be guaranteed.
Virtual Channels
The ioLogik E2262 provides virtual channels so you can easily determine the average or deviation
values for any attached temperature sensor. A virtual channel can operate in Average Mode or
Deviation Mode. In Average Mode, up to 8 physical channels are selected and the virtual channel
reports the average value of the selected channels. In Deviation mode, two physical channels are
selected and the virtual channel reports the difference between the channels.
When using virtual channels, if there are errors on any of the selected physical channels, that
channel’s readings will simply be ignored. You can refer to the LED indicators to see if any errors
are encountered with any of the physical channels.
Note that virtual channels only support temperature units and cannot be used with resistance units.
Any channel that is connected to a mV voltage input will be treated as an error channel.
Calibration
The ioLogik E2262 allows you to calibrate the TC sensor by user. In each channel configuration
section, click “Calibration” and then follow the onscreen instructions to start the TC sensor
calibration. Each calibration needs about 20 seconds (per channel). Please note that you can press
“Reset to default” on the Navigation Panel to reload the factory default value and ignore the user
calibrated value. The default value is calibrated in the factory and is stored in the device.
3-11
ioLogik E2262 User’s Manual
Utilities
Alias Name
Click the Alias Name tab to customize the channel name. You may use names with up to 16
characters. If you already set the Alias Name on I/O Configuration page, the channel name will
appear on Click&Go, Active message, and Web.
Configuring Digital Output Channels
The ioLogik E2262 is equipped with 4 digital output channels that can be set individually to “DO”
or “Pulse Output” mode.
In DO mode, the specification is as follows.
3-12
ioLogik E2262 User’s Manual
Type
DO mode
Utilities
Logic 0 (OFF)
Open
Logic 1 (ON)
Short
In Pulse Output mode, the selected digital output channel will generate a square wave as specified
in the pulse mode parameters. The low and high level widths are entered in multiples of 5 ms, with
a maximum setting of 4,294,967,295, or 248 days, 13 hours, 13 minutes, and 56 seconds.To set the
low level width for 500 ms, you would enter 100 (because 100 × 5 ms = 500 ms). If the low width
value is 500 and the high width value is 500, the pulse output would be a square wave with a
5-second pulse cycle. If continuous pulse output is desired, enter “0” for the number of pulses,
otherwise enter the desired number of pulses between 1 and 4,294,967,295.
Power On Settings
Use this field to set the initial behavior of the DO channel when the ioLogik E2262 is powered on.
You can configure whether or not the DO is set to OFF or ON at power up. For DO channels in
Output Pulse mode, you can configure whether or not the pulse output commences at power up.
Safe Status Settings
Use this field to specify how the DO channel behaves when the network connection is lost. When
the network connection is lost for the amount of time specified in the Host Connection Watchdog,
each output channel will be reset to its Safe Status settings. Note that the Host Connection
Watchdog is disabled by default. If the Host Connection Watchdog is disabled, the Safe Status
settings will have no effect.
You can configure whether or not the DO is set to OFF or ON for Safe Status. For DO channels in
Output Pulse mode, you can configure whether or not the output pulse commences or continues for
Safe Status.
3-13
ioLogik E2262 User’s Manual
Utilities
Test DO
You can test the DO channel by using ioAdmin.
.
DO-DO: set the DO to “ON” or “OFF”
DO-Pulse: activate or stop pulse generation.
Alias Name
Click the Alias Name tab to customize the channel name. You may use names with up to 16
characters. If you already set the Alias Name on I/O Configuration page, the channel name will
appear on Click&Go, Active message, and Web.
Server Settings Tab (Administrator)
You can set up a password, server name, location, date, time zone, and time server in the Server
Settings tab. ioAdmin supports long server names and a location description up to 58 chars. If you
will be using ioEventLog to receive server status reports, such as for warm or cold starts, indicate
the IP address and port number for the PC that will be running ioEventLog in the “System Log”
field. The default port number is 4040.
For additional information, please refer the ioEventLog section later in this chapter.
3-14
ioLogik E2262 User’s Manual
Utilities
Network Tab
The Network tab is where you configure IP settings, Modbus/TCP Alive Check Timeout settings,
DNS settings, Serial settings, SNMP settings, and Web Access settings for the ioLogik E2262.
IP Settings: You can assign a static or dynamic IP address to the ioLogik E2262, as well as the
subnet mask and gateway address. The Accessible IP screen can be used to control network access
to the ioLogik E2262 and attached sensors. The ioLogik will reject all requests that do not
originate from sources listed in the accessible IP list. Leave this list blank in order to allow
requests from any IP address.
Modbus/TCP Alive Check Timeout: The Modbus/TCP Alive Check Timeout is designed to
avoid TCP connection failure. When the host is down, the ioLogik E2262 will continue to wait for
a response from the host. This will cause the TCP port to be indefinitely occupied by the host.
When the Modbus/TCP idle connection timeout interval is enabled, the ioLogik E2262 will close
the TCP connection automatically if there is no TCP activity for the specified time. Please note
that Modbus/TCP connections will be blocked when setting up Accessible IP.
3-15
ioLogik E2262 User’s Manual
Utilities
DNS Settings: Use this field to specify up the IP addresses of up to 2 DNS servers. These two
DNS servers can be used to automatically find available e-mail addresses when using Click&Go
Logic.
Serial Settings: You can view the reserved RS-485 communication parameters here, and you can
set the timeout value for breaks in RS-485 communication. Note that the other serial
communication parameters cannot be modified. If you wish to adjust the baudrate, you will need to
use the physical dial on the back panel of the ioLogik E2262.
SNMP Settings: The ioLogik E2262 supports SNMP v2 (Simple Network Management Protocol)
to allow monitoring of network and I/O devices with SNMP Network Management software. It is
useful in building automation and telecom applications. Use these fields to enable SNMP and set
the read and write community strings.
Web Access Settings: This field enables and disables the ioLogik E2262’s web console. The web
console allows the configuration of many settings using a web browser that is directed to the
server’s IP address. If the web console is not enabled in this field, you will not be able to access
the web console.
Firmware Update Tab
The ioLogik E2262 supports remote firmware updates through the Firmware Update tab. Enter the
path to the firmware file or click on the icon to browse for the file. Click Update to update the
firmware. The wizard will lead you through the process until the server is restarted.
WARNING
Do not interrupt the firmware update process! An interruption in the process could result in
your device becoming unrecoverable.
After the firmware is updated, the ioLogik will restart and you will have to log in again to access
administrator functions.
The firmware on any attached I/O expansion module, such as an ioLogik R2000 server, must be
updated over the RS-485 bus. Firmware on cascaded modules cannot be updated over Ethernet.
3-16
ioLogik E2262 User’s Manual
Utilities
Watchdog Tab
The Watchdog tab is where you configure the Host Connection Watchdog, which is used with the
Safe Status settings to define each DO channel’s response to a lost network connection. When the
Host Connection Watchdog is enabled, the ioLogik E2262 will respond to network disconnections
that exceed the specified amount of time. The ioLogik will respond by resetting DO channels to
their Safe Status settings. By default, the Watchdog is disabled. To enable the Watchdog, make
sure Enable Host Connection Watchdog is checked, set the Timeout value, then click the
Update button.
If the Watchdog is enabled and the network connection has been lost, you will need to return to the
Watchdog Tab in order to resume normal operation. There will be a message saying “Host
Connection Lost”, indicating that Safe Status settings have been activated. Click Clear Alarm to
exit Safe Status and return to normal operation.
Click&Go Logic Tab
The Click&Go Logic tab is where Active Ethernet I/O operation is configured. While traditional
Ethernet I/O involves an I/O server that reacts passively to polling requests from a network host,
Active Ethernet I/O involves an I/O server that actively reports I/O data under user-specified
conditions. Click&Go Logic is a powerful and easy-to-use tool to define the conditions for
reporting I/O data. Please refer to Chapter 5 for more information.
3-17
ioLogik E2262 User’s Manual
Utilities
Changes made in the Click&Go Logic tab are not effective until the ioLogik E2262 is restarted,
just like changes made in other tabs. Note that when an I/O channel is used in Click&Go Logic, its
range and units become fixed and cannot be modified.
Server Context Menu
The Server context menu is accessed by right clicking on the server model name in the navigation
panel.
3-18
ioLogik E2262 User’s Manual
Utilities
Connect
Select this command to have ioAdmin attempt a re-connection over the network to the selected
ioLogik server.
Disconnect
Select this command to have ioAdmin drop the network connection with the selected ioLogik
server.
Delete I/O Server
Select this command to have ioAdmin remove the selected serial I/O.
Add Serial I/O Server
Select this command to manually add a serial I/O server by using its Unit ID.
Restart System
Select this command to restart the selected ioLogik server. You will need to log in as an
administrator to use this function.
Reset to Default
Select this command to reset all settings for the selected ioLogik server, including console
password and IP address, to factory default values. You will need to log in as an administrator to
use this function.
Export System Config
Select this command to export the configuration of the selected ioLogik server to a text file. You
will need to log in as an administrator to use this function. It is strongly recommended you use this
method to back up your configuration after you have finished configuring the ioLogik for your
application.
The following is an example of the exported configuration file:
3-19
ioLogik E2262 User’s Manual
Utilities
Import System Config
Select this command to reload a configuration that was exported to a text file. You will need to log
in as an administrator to use this function. You will need to restart the ioLogik server in order for
the new configuration to take effect. This command can be used to restore a configuration after
loading the factory defaults, or to duplicate a configuration to multiple ioLogiks.
3-20
ioLogik E2262 User’s Manual
Utilities
Using TFTP to Import/Export Configuration
TFTP (Trivial File Transfer Protocol) provides basic FTP functionality in a very simple protocol.
Due to TFTP’s simplicity, it can be implemented using a very small amount of memory, an
important consideration when it was first developed. The ioLogik E2262 supports the use of TFTP
to import or export configuration files.
The following is an example using Windows TFTP and an ioLogik E2262 with an IP address of
192.168.127.254:
1. Enter “TFTP 192.168.127.254 GET ik2262.txt” to get the ioLogik’s configuration file.
2. Enter “TFTP 192.168.127.254 PUT ik2262.txt” to load a configuration file onto the ioLogik.
You must use “ik2262.txt” as the destination filename when copying a configuration file to the
ioLogik E2262. Otherwise, you will receive an error message as shown below:
You can use TFTP in a batch file to transfer configuration files for different units. For example,
you might have two configuration files that need to be copied to two different servers:
ik2262_1.txt for 192.168.127.253, and ik2260_2.txt for 192.168.127.254. A batch file could be
written as follows:
tftp 192.168.127.253 put ik2262_1.txt ik2262.txt
tftp 192.168.127.254 put ik2262_2.txt ik2262.txt
ATTENTION
You can also run TFTP client software, open the configuration file, and enter the remote server’s
IP. Note that both ASCII and Octet mode are supported. When the download process is complete,
the I/O server will reboot. WinTFTP Client Pro is a trademark of WinTFTP. All rights reserved.
3-21
ioLogik E2262 User’s Manual
Utilities
Using ioEventLog
Installing ioEventLog
ioEventLog is a Windows utility provided for the monitoring of the ioLogik E2262 and attached
I/O devices. It can be used from anywhere on the network to monitor the ioLogik E2262.
1.
Installation from CD: Insert the Document and Software CD into the host computer. Run
SETUP.EXE, which is located in the root directory. The installation program will guide you
through the installation process and install the ioEventLog utility.
2.
Open ioEventLog: After installation is finished, run ioEventLog from Start Æ Program Files
Æ Moxa Æ IO Server Æ Utility ÆioEventLog.
Basic Functions
ioEventLog is installed along with ioAdmin form the Document and Software CD. It is designed
to help you keep a record of ioLogik status events over the network. The log is stored on the
Windows PC. You will need to set up your ioLogik to send status events to the PC’s IP address.
The following events are monitored:
y cold start
y warm start
For each event, the following information is provided. The log can be sorted by any of these fields:
y Event type
y Event date and time
y ioLogik’s source name
y Source IP
y Destination IP
y Host date and time
y Source model
3-22
ioLogik E2262 User’s Manual
Utilities
Configuration
In the System menu, select Settings to configure ioEventLog.
The Alarm Listen Port is the TCP port number that will be monitored for status events. You can
modify this setting as necessary to receive signals through a firewall. It will need to match the
settings for the ioLogik that is being monitored.
The Log Directory is where the log files will be stored. The default directory is C:\Program
Files\Moxa\ioEventLog\log. A separate log file is created for each day, with file names assigned
automatically.
You can also select the color of each event type in the log.
3-23
ioLogik E2262 User’s Manual
Utilities
Checking Connected Devices
You can see which I/O servers is already connected to ioEventLog by selecting Connected Device
List from the Connection menu. You will be prompted to view which devices are connected.
Opening Log Files
You can view previously saved logs by selecting Open from the Log menu. You will be prompted
for the data that you wish to view.
The logs for the day that you select will be displayed in the Alarm Log Viewer window.
Clearing the Log
If you wish to clear the log, you can select Clear from Log menu. This will clear all events for the
current day. The cleared events will not be saved in that day’s logs. After the logs are cleared, new
events will be displayed and recorded as usual.
3-24
4
Chapter 4
Using the Web Console
You can use the ioLogik E2262’s built in web console to configure many options.
The following topics are covered:
‰ Introduction to the Web Console
‰ Basic Settings
‰ Network Settings
¾ General Settings
¾ Ethernet Configuration
¾ RS-485 Settings
‰ I/O Settings
¾ TC Channels
¾ DO Channels
‰ System Management
¾ Accessible IP Settings
¾ SNMP Agent
¾ Network Connection
¾ Firmware Update
¾ Import System Config
¾ Export System Config
‰ LCM
‰ Change Password
‰ Load Factory Default
‰ Save/Restart
ioLogik E2262 User’s Manual
Using the Web Console
Introduction to the Web Console
The ioLogik E2262 web console is a browser-based configuration utility. When the ioLogik E2262
is connected to your network, you can enter the server’s IP address in your web browser to access
the web console. Note that although most configuration options are available in the web console,
some settings are only available through ioAdmin. Furthermore, the web console can be disabled
under Web Access Settings in ioAdmin. If you are unable to access the web console, check the
Web Access Settings in ioAdmin.
Main
Window
Navigation
Panel
The left panel is the navigation panel and contains an expandable menu tree for navigating among
the various settings and categories. When you click on a menu item in the navigation panel, the
main window will display the corresponding options for that item. Configuration changes can then
be made in the main window. For example, if you select Basic Settings in the navigation panel, the
main window will show a page of basic settings that you can configure.
You must click the Submit button after making configuration changes. The Submit button will be
located at the bottom of every page that has configurable settings. If you navigate to another page
without clicking the Submit button, your changes will not be retained.
Submitted changes will not take effect until they are saved and the ioLogik E2262 is restarted!
You can save and restart the server in one step by clicking the Save/Restart button after you
submit a change. If you need to make several changes before restarting, you can save your changes
without restarting by selecting Save/Restart in the navigation panel. If you restart the ioLogik
E2262 without saving your configuration, the ioLogik E2262 will discard all submitted changes.
Basic Settings
On the Basic Settings page, you can set the ioLogik E2262’s system time or provide the IP address
of a time server for time synchronization.
4-2
ioLogik E2262 User’s Manual
Using the Web Console
Network Settings
General Settings
On the General Settings page, you can assign a server name and location to assist you in
differentiating between different I/O servers. You can also enable the Host Communication
Watchdog and define the timeout value.
When enabled, the Host Connection Watchdog activates Safe Status settings for DO channels
when the ioLogik E2262 loses its network connection for the specified amount of time. By default,
the Watchdog is disabled. You can use ioAdmin to configure each DO channel’s Safe Status
setting.
To enable the Watchdog, make sure that Enable connection watchdog is checked, set the timeout
value, and restart the server.
Ethernet Configuration
On the Ethernet Configuration page, you can set up a static or dynamic IP address for the ioLogik
E2262, as well as the subnet mask and gateway address.
4-3
ioLogik E2262 User’s Manual
Using the Web Console
RS-485 Settings
On the RS-485 Settings page, you can view the serial communication parameters, but no
configuration changes are allowed. The baudrate can only be configured by the physical dial on
the back of the ioLogik E2262. This is a reserved function.
I/O Settings
TC Channels
On the TC Channels page, you can view the status of channels TC-00 through TC-15, which
includes both physical and virtual channels. You can click the Channel Name to enter settings
page on which can set the Alias Name.
4-4
ioLogik E2262 User’s Manual
Using the Web Console
You can click on each channel to enable or disable it, or to configure the TC input mode. When a
channel has been disabled, the sample rate of the remaining channels will be increased
automatically.
The following table is a list of supported sensor types and ranges.
Type
Temperature Range
J
Count Range
0ºC to 750ºC
0 to
7,500
K
-200ºC to 1250ºC
-2,000 to 12,500
T
-200ºC to 350ºC
-2,000 to
3,500
E
-200ºC to 900ºC
-2,000 to
9,000
R
-50ºC to 1600ºC
-500 to 16,000
S
-50ºC to 1760ºC
-500 to 17,600
B
600ºC to 1700ºC
6,000 to 17,000
N
-200ºC to 1300ºC
-2,000 to 13,000
2.3 μV
- 78.126mV to + 78.126mV
-781,260 to 781,260
1.15 μV
- 39.062mV to + 39.062mV
-390,620 to 390,620
0.5 μV
- 19.532mV to + 19.532mV
-195,320 to 195,320
Channels 8 through 15 are virtual channels. You can click on a virtual channel to configure
whether it will return current averages or deviations for the specified physical channels (TC-00
through TC-07).
4-5
ioLogik E2262 User’s Manual
Using the Web Console
DO Channels
On the DO Channels page, you can configure each DO (digital output) channel by clicking on the
channel. DO Channels can operate in DO mode or Pulse Output mode. In DO mode, output is
either on or off. In Pulse Output mode, a configurable square wave is generated.
You can use the Power On Setting field to specify the channel’s status when the ioLogik E2262 is
powered on, and the Safe Status Setting field to specify the channel’s status if the network is
disconnected. Note that Safe Status is controlled by the Host Connection Watchdog, which is
disabled by default. If the Host Connection Watchdog is disabled, the channels’ Safe Status
settings will have no effect.
4-6
ioLogik E2262 User’s Manual
Using the Web Console
System Management
Accessible IP Settings
On the Accessible IP Settings page, you can control network access to the ioLogik E2262. When
the accessible IP list is enabled, a host’s IP address must be listed in order to have access to the
ioLogik E2262.
You can add a specific address or range of addresses by using a combination of IP address and
netmask, as follows:
z
z
z
To allow access to a specific IP address
Enter the IP address in the corresponding field; enter 255.255.255.255 for the netmask.
To allow access to hosts on a specific subnet
For both the IP address and netmask, use 0 for the last digit (e.g., 192.168.1.0 and
255.255.255.0).
To allow unrestricted access
Deselect the Enable the accessible IP list option.
Refer to the following table for additional configuration examples.
Allowed Hosts
Any host
192.168.1.120
192.168.1.1 to 192.168.1.254
192.168.0.1 to 192.168.255.254
192.168.1.1 to 192.168.1.126
192.168.1.129 to 192.168.1.254
IP address/Netmask
Disable
192.168.1.120 / 255.255.255.255
192.168.1.0 / 255.255.255.0
192.168.0.0 / 255.255.0.0
192.168.1.0 / 255.255.255.128
192.168.1.128 / 255.255.255.128
4-7
ioLogik E2262 User’s Manual
Using the Web Console
SNMP Agent
On the SNMP Agent page, you can enable SNMP and set the read and write community strings.
The ioLogik E2262 supports SNMP v2 (Simple Network Management Protocol) to allow
monitoring of network and I/O devices with SNMP Network Management software. It is useful in
building automation and telecom applications.
Network Connection
On the Network Connection page, you can view the TCP connections from other hosts. This can
assist you in the management of your devices.
Firmware Update
On the Firmware Update page, you can load new or updated firmware onto the ioLogik.
4-8
ioLogik E2262 User’s Manual
Using the Web Console
Import System Config
On the Import System Config page, you can import a configuration onto the ioLogik. The
configuration file must have been generated by ioAdmin or through the web console. This function
can be used to duplicate settings between ioLogiks. You will be prompted for the location of the
configuration file (i.e., “ik2262.txt”).
Export System Config
On the Export System Config page, you can save the ioLogik’s configuration into a file for backup
or import into another ioLogik server.
LCM
If you have installed the optional LCM, you can view the LCM’s status and firmware details on
the LCM page.
4-9
ioLogik E2262 User’s Manual
Using the Web Console
Change Password
When changing the ioLogik E2262’s password settings, you will first need to enter the old
password. Leave this blank if you are setting up password protection for the first time. To set up a
new password or change the existing password, enter your desired password under both New
password and Confirm password. To remove password protection, leave the New password and
Confirm password fields blank.
ATTENTION
If you forget the password, the ONLY way to configure the ioLogik E2262 is by using the reset
button to load the factory defaults.
Before you set a password for the first time, it is a good idea to complete the ioLogik’s
configuration and export the configuration to a file. The configuration can then be easily loaded
imported back into the ioLogik E2262 if it has been reset to factory defaults.
Load Factory Default
This function will reset all of the ioLogik E2262’s settings to the factory default values. All
previous settings including the console password will be lost.
Save/Restart
If you change the configuration, do not forget to reboot the system.
4-10
5
Chapter 5
Click&Go Logic
Click&Go Logic was developed by Moxa to provide an easy way to program your ioLogik E2262
for active I/O messaging. In the chapter, we will show you how Click&Go Logic works and how
to use it to develop your active I/O messaging program.
The following topics are covered in this chapter:
‰ Overview
‰ Features
‰ Click&Go Logic Basics
¾ Working with Rules
‰ Defining Logic Rules
¾ Summary of IF/THEN Parameters
¾ IF Conditions
¾ THEN Actions
‰ Working with Click&Go Rulesets
¾ Activating the Ruleset
¾ Ruleset Management Bar
¾ Ruleset Import/Export
ioLogik E2262 User’s Manual
Click&Go Logic
Overview
The ioLogik E2262’s Active Ethernet I/O system eliminates the need for host computers to
continually poll I/O devices for status. Instead, the server itself is able to monitors the status of
each I/O device and take the appropriate action when the I/O status satisfies a user-defined
condition. For example, the ioLogik E2262 could be configured to send a TCP/UDP message only
when a temperature sensor attached to TC-00 reports a reading of 85°C. This structure results in a
much improved response time and a much reduced load on the host computer’s CPU and on
network bandwidth.
Click&Go Logic was developed to provide an easy and intuitive way to configure when and how
I/O information is transmitted over the network. Using simple If – Then statements, you set the
conditions that need to be satisfied and the resulting actions. Up to three conditions and three
actions can be combined in any one rule, and up to 16 rules can be defined in a ruleset. Each
SNMP trap or TCP/UDP message can be transmitted to up to 10 computers simultaneously.
Features
Click&Go Logic’s key features are as follows:
y Easy local logic control with intuitive If/Then construction
y Up to 16 user-defined rules
y Up to 3 I/O-based conditions and 3 DO or network actions per rule
y Email, TCP, UDP, or SNMP trap for active I/O messaging
y Customizable message content with dynamic fields for time, date, IP address, and more
y Up to 10 simultaneous IP destinations for TCP/UDP messaging
y Configurable interval for time-triggered events
Click&Go Logic Basics
To use Click&Go Logic, open ioAdmin and log on as an administrator on the Server Settings tab.
Once you are logged on, go to the Click&Go Logic tab. It should appear as follows:
1
2
3
5-2
ioLogik E2262 User’s Manual
Click&Go Logic
Click&Go Logic Tab
1. Logic Name: In this field, you can assign a name for the set of rules.
2. Rules List: In this area, each rule’s conditions, actions, and status are displayed.
3. Ruleset Management Bar: In this area, you manage the ruleset
Working with Rules
Rules are the building blocks of your Active Ethernet I/O system. With rules, you define the exact
trigger conditions for transmission of I/O information as well as the content and destination of that
information. DO operation can also be automated based on TC trigger conditions.
In the main screen, you will see the list of rules in the current ruleset. Double click on a rule to
open that rule’s configuration window, or double click on an empty rule to start a new rule.
The configuration window is where the rule is defined. Basic If-Then logic is used to set up
temperature event-based triggers.
The Equivalent Logic Statement at the bottom shows a real-time text-based summary of the rule
that you are defining. It can be a useful way to make sure that the rule is designed as you intended.
ATTENTION
The unit of measurement is defined on the I/O configuration tab. When an I/O channel is
being used in a Click&Go Logic rule, the channel’s range and units can not be modified.
5-3
ioLogik E2262 User’s Manual
Click&Go Logic
Defining Logic Rules
Each rule consists of two columns. The IF column defines I/O conditions and the THEN column
defines actions. When the ioLogik detects that the IF conditions have been satisfied, the THEN
actions will be performed.
Summary of IF/THEN Parameters
IF Conditions
TC-x
Time Trigger
(Condition #1 only)
Operators
=,>,<,>=,<=
Remark
Max value 4,294,967,295
N/A
Max value 4,294,967,295 for
time interval
THEN Actions
DO-x
Pulse Output-x
SNMP Trap
Active Message
Email
Operators
ON/OFF
Start/Stop
1 to 20
N/A
N/A
Remark
Depends on DO type
Depends on DO type
Details below
Details below
Details below
IF Conditions
Under the IF column, you can set up to 3 IF conditions. As soon as the IF conditions are satisfied,
the THEN actions are performed. For example, an alarm can be activated when a temperature
exceeds a certain level. Use the pull downs to specify the conditions and units of measurement
(e.g., TC-00 > 60°C). The available operators are =, <, >, <=, and >=.
You may want an action to be repeated for as long as the conditions remain satisfied. For example,
instead of simply turning on an alarm, you may wish to send an alert message every five minutes
for as long as the temperature exceeds a certain level. You can set a repeating interval in the
Check every ___ sec field. The THEN action will be repeated at the specified interval for as long
as the set of IF conditions is satisfied.
Under Relation between condition, select AND to specify that all conditions must be satisfied for
the action to take place; select OR to specify that the action should occur if any one of the
conditions is satisfied.
Instead of performing an action under specified I/O conditions, you may wish to set up a heartbeat
status message or action that repeats at regular intervals as long as the I/O server is operational. In
this case, you can set up a Time Trigger rule as the first IF condition. For example, you can set a
3600 second interval so that a TCP status message is sent every hour.
THEN Actions
Under the THEN column, you can set up to 3 actions that will be performed if the conditions under
the IF column are satisfied. The 3 actions can be any combination of DO status setting, SNMP
Trap, Active Message (by TCP/UDP), or E-mail. For SNMP trap, Active Message, and E-mail
actions, use the following memo icon to additional parameters:
5-4
ioLogik E2262 User’s Manual
Click&Go Logic
Active Message
Select Active Message for active I/O messaging over TCP or UDP. Click the memo icon to
configure the message and parameters. Note that TCP and UDP cannot be used at the same time
within a ruleset – all rules must use the same protocol.
After clicking the memo icon, you can enter your desired message in the Message Content window.
Dynamic fields such as time, date, IP address, and I/O status can be inserted in your message by
clicking on the Keyword Lookup button. Up to 10 IP destinations for the message can be
specified in the Message Receiver list. The default Message Port is 9000, and this can be modified
as necessary to work with your firewall.
By default, messages are sent in ASCII, although ioAdmin can display the message in HEX in
Message Monitor.
Messages can also be entered in HEX by selecting the “Send as HEX” checkbox. When sending a
message in HEX, each HEX value must be delimited by commas. Certain control characters will
only appear in the Message Monitor when “Toggle HEX” is selected, as in the following example.
5-5
ioLogik E2262 User’s Manual
Click&Go Logic
SNMP Trap
Select SNMP trap along with a trap number between 1 and 20. You may need to consult with your
network administrator to determine how trap numbers will be used and defined in your network.
Click the memo icon to specify up to 10 IP addresses to receive the SNMP trap. You can also bind
the status of up to three I/O channels within each trap.
5-6
ioLogik E2262 User’s Manual
Click&Go Logic
E-mail
Select E-mail to send a user-defined email to the specified addresses. Click the memo icon to enter
the desired message and the intended recipients. Dynamic fields such as time, date, IP address, and
I/O status can be inserted in your message by clicking on the Keyword Lookup button.
If you already set the Alias Name on I/O Configuration page, the channel will be replaced here.
To select a recipient, you must first add the recipient’s e-mail address to the Available receivers
list. You can then use the finger icons to move e-mail addresses to and from the Receivers list. To
edit an e-mail address, click the memo icon. Note that the Available receivers list will already
contain a list of names if you provided the DNS server information in the Network Settings tab.
Enter your own e-mail address in the From Address field.
Under Mail Server Settings, you must configure the IP address of the SMTP server with your
username and password. Since the ioLogik E2262 supports DNS, you can enter the domain name
of the SMTP server.
5-7
ioLogik E2262 User’s Manual
Click&Go Logic
Working with Click&Go Rulesets
Activating the Ruleset
A Click&Go Logic ruleset contains up to 16 rules that act as the brain of your Active Ethernet I/O
system. The Click&Go Logic tab lists the rules in the current ruleset, which work together to
determine what I/O information is sent, who it is sent to, how it is sent, and under what I/O
conditions it is sent. This simple but powerful tool is significantly more efficient with network and
CPU resources than traditional blanket polling methods.
By default, the ioLogik E2262 operates as a passive remote server. In order to operate as an Active
Ethernet I/O server, you must define a ruleset and then perform the following three steps:
1. The ruleset must be downloaded from ioAdmin onto the ioLogik E2262. You can do so by
clicking on Download in the Ruleset Management bar.
2. After the ruleset has been downloaded, the ioLogik E2262 must be restarted. You can do this by
right clicking on the server name in the navigation panel in ioAdmin and selecting Restart. Do
not use the reset button, as that will load all factory defaults and erase your ruleset from
memory.
3. After the ioLogik E2262 has restarted, the ruleset must be activated for Active Ethernet I/O
operation. First, you will need to log in as an administrator again in ioAdmin’s Server Setting
tab. Once you have logged in, go to the Click&Go Logic tab and click Run in the Ruleset
Management bar. This will activate the ruleset and the ioLogik E2262 will begin Active
Ethernet I/O operation.
When the ruleset has been activated, it will remain active even when the ioLogik E2262 is
disconnected from the host computer or from the network. If the ioLogik E2262 is turned off,
Active Ethernet I/O operation will resume when it is turned back on. This allows you to use the
ioLogik E2262 for PC-independent automation.
Ruleset Management Bar
y Clear: The Clear command erases the ruleset in both ioAdmin and in the ioLogik E2262.
y Retrieve: The Retrieve command copies the ruleset from the ioLogik E2262 into ioAdmin.
y Download: The Download command copies the ruleset from ioAdmin onto the ioLogik E2262.
y Run: The Run command starts Active Ethernet I/O operation using the ruleset that the ioLogik
E2262 booted up with.
y Stop: The Stop command stops Active Ethernet I/O operation.
Ruleset Import/Export
Although rulesets alone cannot be imported and exported, the entire system configuration
including the current ruleset can be imported and exported. As you make changes to a ruleset, you
can export the system configuration in order to save that ruleset.
5-8
A
Appendix A
Liquid Crystal Display Module (LCM)
The ioLogik E2262 supports an optional detachable Liquid Crystal Display Module (LCM) for
easier field maintenance. The LCM is hot-pluggable and can be used to configure the network
settings or display other settings. When plugged in, the LCM displays the ioLogik E2262 “home
page,” and pressing any button takes you into the settings and configuration.
LCM Controls
The up and down buttons navigate between the current options. The right and left buttons enter
and exit the submenus. The center button is used when modifying settings or restarting the server.
Button Function
Up
go to the previous item
Down
go to the next item
Left
exit the current submenu and return to the previous menu (go up one level)
Right
enter the selected submenu (go down one level)
Center enter/exit editing mode
An “e” in the upper right hand corner of the display indicates that the parameter can be modified.
Press the center button on the LCM to modify that parameter’s settings.
LCM Options
Display
Explanation / Actions
<ioLogik E2262>
This is the default “home page” showing the IP address. Press
the down button to view the submenus.
<ioLogik E2262>
server
Enter this submenu to display information about the specific
server you are viewing:
z serial number
z name
z location
z E2262 f/w ver
z lcm f/w ver
z model name
ioLogik E2262 User’s Manual
Display
<ioLogik E2262>
network
Liquid Crystal Display Module (LCM)
Explanation / Actions
Enter this submenu to display information and settings for the
network:
z ethernet link
z MAC address
z IP mode
z IP address
z netmask
z gateway
z DNS server-1
z DNS server-2
<ioLogik E2262>
click&go
Enter this submenu to display information about the ruleset
being used by the active I/O system.
z name
z status
<ioLogik E2262>
serial port
Enter this submenu to display the RS-485 cascade port settings.
<ioLogik E2262>
i/o setting
<ioLogik E2262>
console
<ioLogik E2262>
ping
<ioLogik E2262>
save/restart
Enter this submenu to access I/O channel status. Here are
examples of settings that you might see:
z TC-00 XXX
Press up or down to navigate through the different I/O channels
without having to go back to the previous menu.
Enter this submenu to see if the web console is enabled or
disabled.
Select this option to enter an IP address to ping. If you get a
“timeout” error, it indicates that the E2262 cannot reach that IP
address. Otherwise, the display will show the response time.
Enter this submenu to display the restart now submenu. Enter
the restart now submenu to display the restart option. Press the
center button to modify this option, then select enable to save
changes and reboot the I/O server. The disable option has no
effect.
WARNING
Any configuration changes that are made through the LCM will not take effect until the ioLogik
E2262 is restarted.
A-2
B
Appendix B
Modbus Mappings
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference
00001
Address
0x0000
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
00015
00016
00017
00018
00019
00020
00021
00022
00023
00024
00025
00026
00027
00028
00029
00030
00031
00032
00033
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
0x000C
0x000D
0x000E
0x000F
0x0010
0x0011
0x0012
0x0013
0x0014
0x0015
0x0016
0x0017
0x0018
0x0019
0x001A
0x001B
0x001C
0x001D
0x001E
0x001F
0x0020
Data Type
Description
1bit
CH0 TC Reset Minimum Value
<R> Always 0
<W> 1=Reset to current value,
1 bit
CH1 TC Reset Minimum Value
1 bit
CH2 TC Reset Minimum Value
1 bit
CH3 TC Reset Minimum Value
1 bit
CH4 TC Reset Minimum Value
1 bit
CH5 TC Reset Minimum Value
1 bit
CH6 TC Reset Minimum Value
1 bit
CH7 TC Reset Minimum Value
1 bit
Virtual CH8 TC Reset Maximum Value
1 bit
Virtual CH9 TC Reset Minimum Value
1 bit
Virtual CH10 TC Reset Minimum Value
1 bit
Virtual CH11 TC Reset Minimum Value
1 bit
Virtual CH12 TC Reset Minimum Value
1 bit
Virtual CH13 TC Reset Minimum Value
1 bit
Virtual CH14 TC Reset Minimum Value
1 bit
Virtual CH15 TC Reset Minimum Value
1 bit
CH0 TC Reset Maximum Value
1 bit
CH1 TC Reset Maximum Value
1 bit
CH2 TC Reset Maximum Value
1 bit
CH3 TC Reset Maximum Value
1 bit
CH4 TC Reset Maximum Value
1 bit
CH5 TC Reset Maximum Value
1 bit
CH6 TC Reset Maximum Value
1 bit
CH7 TC Reset Maximum Value
1 bit
Virtual CH8 TC Reset Maximum Value
1 bit
Virtual CH9 TC Reset Maximum Value
1 bit
Virtual CH10 TC Reset Maximum Value
1 bit
Virtual CH11 TC Reset Maximum Value
1 bit
Virtual CH12 TC Reset Maximum Value
1 bit
Virtual CH13 TC Reset Maximum Value
1 bit
Virtual CH14 TC Reset Maximum Value
1 bit
Virtual CH15 TC Reset Maximum Value
1 bit
CH0 TC Enable
<RW> 0=Disable, 1=Enable
ioLogik E2262 User’s Manual
Modbus Mappings
00034
00035
00036
00037
00038
00039
00040
00041
0x0021
0x0022
0x0023
0x0024
0x0025
0x0026
0x0027
0x0028
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
00042
00043
00044
00045
0x0029
0x002A
0x002B
0x002C
1 bit
1 bit
1 bit
1 bit
00046
00047
00048
00049
0x002D
0x002E
0x002F
0x0030
1 bit
1 bit
1 bit
1 bit
00050
00051
00052
00053
0x0031
0x0032
0x0033
0x0034
1 bit
1 bit
1 bit
1 bit
00054
00055
00056
00057
0x0035
0x0036
0x0038
1 bit
1 bit
1 bit
1 bit
00058
00059
00060
00061
0x0039
0x003A
0x003B
0x003C
1 bit
1 bit
1 bit
1 bit
00062
00063
00064
0x003D
0x003E
0x003F
1 bit
1 bit
1 bit
CH1 TC Enable
CH2 TC Enable
CH3 TC Enable
CH4 TC Enable
CH5 TC Enable
CH6 TC Enable
CH7 TC Enable
CH0 DO Status
<RW> 0=OFF, 1=ON
CH1 DO Status
CH2 DO Status
CH3 DO Status
CH0 DO Power-On Status
<RW> 0=OFF, 1=ON
CH1 DO Power-On Status
CH2 DO Power-On Status
CH3 DO Power-On Status
CH0 DO Safe Status
<RW> 0=OFF, 1=ON
CH1 DO Safe Status
CH2 DO Safe Status
CH3 DO Safe Status
CH0 DO Pulse Output Status
<RW> 0=Stop, 1=Start
CH1 DO Pulse Output Status
CH2 DO Pulse Output Status
CH3 DO Pulse Output Status
CH0 DO Power-On Pulse Output Status
<RW> 0=Stop, 1=Start
CH1 DO Power-On Pulse Output Status
CH2 DO Power-On Pulse Output Status
CH3 DO Power-On Pulse Output Status
CH0 DO Safe Mode Pulse Output Status
<RW> 0=Stop, 1=Start
CH1 DO Safe Mode Pulse Output Status
CH2 DO Safe Mode Pulse Output Status
CH3 DO Safe Mode Pulse Output Status
B-2
ioLogik E2262 User’s Manual
Modbus Mappings
3xxxx Read Only Registers (Function 4)
Reference
30001
Address
0x0000
30002
0x0001
30003
30004
30005
30006
30007
30008
30009
30010
30011
30012
30013
30014
30015
30016
30017
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
0x000C
0x000D
0x000E
0x000F
0x0010
30018
0x0011
30019
30020
30021
30022
30023
30024
30025
30026
30027
30028
30029
30030
30031
30032
30033
0x0012
0x0013
0x0014
0x0015
0x0016
0x0017
0x0018
0x0019
0x001A
0x001B
0x001C
0x001D
0x001E
0x001F
0x0020
30034
0x0021
30035
0x0022
Data Type
Description
1 word
CH0 TC Value Hi Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
1 word
CH0 TC Value Lo Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
1 word
CH1 TC Value Hi Word
1 word
CH1 TC Value Lo Word
1 word
CH2 TC Value Hi Word
1 word
CH2 TC Value Lo Word
1 word
CH3 TC Value Hi Word
1 word
CH3 TC Value Lo Word
1 word
CH4 TC Value Hi Word
1 word
CH4 TC Value Lo Word
1 word
CH5 TC Value Hi Word
1 word
CH5 TC Value Lo Word
1 word
CH6 TC Value Hi Word
1 word
CH6 TC Value Lo Word
1 word
CH7 TC Value Hi Word
1 word
CH7 TC Value Lo Word
1 word
Virtual CH8 TC Value Hi Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
1 word
Virtual CH8 TC Value Lo Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
1 word
Virtual CH9 TC Value Hi Word
1 word
Virtual CH9 TC Value Lo Word
1 word
Virtual CH10 TC Value Hi Word
1 word
Virtual CH10 TC Value Lo Word
1 word
Virtual CH11 TC Value Hi Word
1 word
Virtual CH11 TC Value Lo Word
1 word
Virtual CH12 TC Value Hi Word
1 word
Virtual CH12 TC Value Lo Word
1 word
Virtual CH13 TC Value Hi Word
1 word
Virtual CH13 TC Value Lo Word
1 word
Virtual CH14 TC Value Hi Word
1 word
Virtual CH14 TC Value Lo Word
1 word
Virtual CH15 TC Value Hi Word
1 word
Virtual CH15 TC Value Lo Word
1 word
CH0 TC Minimum Value Hi Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
1 word
CH0 TC Minimum Value Lo Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
1 word
CH1 TC Minimum Value Hi Word
B-3
ioLogik E2262 User’s Manual
Modbus Mappings
30036
30037
30038
30039
30040
30041
30042
30043
30044
30045
30046
30047
30048
30049
0x0023
0x0024
0x0025
0x0026
0x0027
0x0028
0x0029
0x002A
0x002B
0x002C
0x002D
0x002E
0x002F
0x0030
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
30050
0x0031
1 word
30051
30052
30053
30054
30055
30056
30057
30058
30059
30060
30061
30062
30063
30064
30065
0x0032
0x0033
0x0034
0x0035
0x0036
0x0037
0x0038
0x0039
0x003A
0x003B
0x003C
0x003D
0x003E
0x003F
0x0040
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
30066
0x0041
1 word
30067
30068
30069
30070
30071
30072
30073
30074
30075
30076
30077
0x0042
0x0043
0x0044
0x0045
0x0046
0x0047
0x0048
0x0049
0x004A
0x004B
0x004C
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
B-4
CH1 TC Minimum Value Lo Word
CH2 TC Minimum Value Hi Word
CH2 TC Minimum Value Lo Word
CH3 TC Minimum Value Hi Word
CH3 TC Minimum Value Lo Word
CH4 TC Minimum Value Hi Word
CH4 TC Minimum Value Lo Word
CH5 TC Minimum Value Hi Word
CH5 TC Minimum Value Lo Word
CH6 TC Minimum Value Hi Word
CH6 TC Minimum Value Lo Word
CH7 TC Minimum Value Hi Word
CH7 TC Minimum Value Lo Word
Virtual CH8 TC Minimum Value Hi Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
Virtual CH8 TC Minimum Value Lo Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
Virtual CH9 TC Minimum Value Hi Word
Virtual CH9 TC Minimum Value Lo Word
Virtual CH10 TC Minimum Value Hi Word
Virtual CH10 TC Minimum Value Lo Word
Virtual CH11 TC Minimum Value Hi Word
Virtual CH11 TC Minimum Value Lo Word
Virtual CH12 TC Minimum Value Hi Word
Virtual CH12 TC Minimum Value Lo Word
Virtual CH13 TC Minimum Value Hi Word
Virtual CH13 TC Minimum Value Lo Word
Virtual CH14 TC Minimum Value Hi Word
Virtual CH14 TC Minimum Value Lo Word
Virtual CH15 TC Minimum Value Hi Word
Virtual CH15 TC Minimum Value Lo Word
CH0 TC Maximum Value Hi Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
CH0 TC Maximum Value Lo Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
CH1 TC Maximum Value Hi Word
CH1 TC Maximum Value Lo Word
CH2 TC Maximum Value Hi Word
CH2 TC Maximum Value Lo Word
CH3 TC Maximum Value Hi Word
CH3 TC Maximum Value Lo Word
CH4 TC Maximum Value Hi Word
CH4 TC Maximum Value Lo Word
CH5 TC Maximum Value Hi Word
CH5 TC Maximum Value Lo Word
CH6 TC Maximum Value Hi Word
ioLogik E2262 User’s Manual
Modbus Mappings
30078
30079
30080
30081
0x004D
0x004E
0x004F
0x0050
1 word
1 word
1 word
1 word
30082
0x0051
1 word
30083
30084
30085
30086
30087
30088
30089
30090
30091
30092
30093
30094
30095
30096
0x0052
0x0053
0x0054
0x0055
0x0056
0x0057
0x0058
0x0059
0x005A
0x005B
0x005C
0x005D
0x005E
0x005F
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
CH6 TC Maximum Value Lo Word
CH7 TC Maximum Value Hi Word
CH7 TC Maximum Value Lo Word
Virtual CH8 TC Maximum Value Hi Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
Virtual CH8 TC Maximum Value Lo Word
<R> 0~4294967295,
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
Virtual CH9 TC Maximum Value Hi Word
Virtual CH9 TC Maximum Value Lo Word
Virtual CH10 TC Maximum Value Hi Word
Virtual CH10 TC Maximum Value Lo Word
Virtual CH11 TC Maximum Value Hi Word
Virtual CH11 TC Maximum Value Lo Word
Virtual CH12 TC Maximum Value Hi Word
Virtual CH12 TC Maximum Value Lo Word
Virtual CH13 TC Maximum Value Hi Word
Virtual CH13 TC Maximum Value Lo Word
Virtual CH14 TC Maximum Value Hi Word
Virtual CH14 TC Maximum Value Lo Word
Virtual CH15 TC Maximum Value Hi Word
Virtual CH15 TC Maximum Value Lo Word
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference
40001
Address
0x0000
40002
0x0001
40003
40004
40005
40006
40007
40008
40009
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
40010
0x0009
40011
0x000A
40012
0x000B
40013
0x000C
Data Type
Description
1 word
CH0 DO Pulse Output Count Value Hi Word
<RW> 0~4294967295
1 word
CH0 DO Pulse Output Count Value Lo Word
<RW> 0~4294967295
1 word
CH1 DO Pulse Output Count Value Hi Word
1 word
CH1 DO Pulse Output Count Value Lo Word
1 word
CH2 DO Pulse Output Count Value Hi Word
1 word
CH2 DO Pulse Output Count Value Lo Word
1 word
CH3 DO Pulse Output Count Value Hi Word
1 word
CH3 DO Pulse Output Count Value Lo Word
1 word
CH0 DO Pulse Output Low Signal Width – Hi
Word
<RW> 0~4294967295
1 word
CH0 DO Pulse Output Low Signal Width –
Lo Word
<RW> 0~4294967295
1 word
CH1 DO Pulse Output Low Signal Width – Hi
Word
1 word
CH1 DO Pulse Output Low Signal Width – Lo
Word
1 word
CH2 DO Pulse Output Low Signal Width – Hi
Word
B-5
ioLogik E2262 User’s Manual
Modbus Mappings
40014
0x000D
1 word
40015
0x000E
1 word
40016
0x000F
1 word
40017
0x0010
1 word
40018
0x0011
1 word
40019
0x0012
1 word
40020
0x0013
1 word
40021
0x0014
1 word
40022
0x0015
1 word
40023
0x0016
1 word
40024
0x0017
1 word
40025
0x0018
1 word
40026
40027
40028
40029
0x0019
0x001A
0x001B
0x001C
1 word
1 word
1 word
1 word
40030
40031
40032
40033
40034
40035
40036
40037
0x001D
0x001E
0x001F
0x0020
0x0021
0x0022
0x0023
0x0024
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
40038
40039
40040
40041
40042
40043
40044
40045
0x0025
0x0026
0x0027
0x0028
0x0029
0x002A
0x002B
0x002C
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
B-6
CH2 DO Pulse Output Low Signal Width – Lo
Word
CH3 DO Pulse Output Low Signal Width – Hi
Word
CH3 DO Pulse Output Low Signal Width – Lo
Word
CH0 DO Pulse Output High Signal Width –
Hi Word
<RW> 0~4294967295
CH0 DO Pulse Output High Signal Width –
Lo Word
<RW> 0~4294967295
CH1 DO Pulse Output High Signal Width – Hi
Word
CH1 DO Pulse Output High Signal Width – Lo
Word
CH2 DO Pulse Output High Signal Width – Hi
Word
CH2 DO Pulse Output High Signal Width – Lo
Word
CH3 DO Pulse Output High Signal Width – Hi
Word
CH3 DO Pulse Output High Signal Width – Lo
Word
CH0 DO Operation Mode
<RW> 0=DO Mode, 1=Pulse Output
Mode
CH1 DO Operation Mode
CH2 DO Operation Mode
CH3 DO Operation Mode
CH0 TC Engineering Unit
0=Celsius, 1=Fahrenheit, 2=millivolt
CH1 TC Engineering Unit
CH2 TC Engineering Unit
CH3 TC Engineering Unit
CH4 TC Engineering Unit
CH5 TC Engineering Unit
CH6 TC Engineering Unit
CH7 TC Engineering Unit
Virtual CH8 TC Engineering Unit
0=Celsius, 1=Fahrenheit, 2= millivolt
Virtual CH9 TC Engineering Unit
Virtual CH10 TC Engineering Unit
Virtual CH11 TC Engineering Unit
Virtual CH12 TC Engineering Unit
Virtual CH13 TC Engineering Unit
Virtual CH14 TC Engineering Unit
Virtual CH15 TC Engineering Unit
CH0 TC Sensor Type
0=J Type
ioLogik E2262 User’s Manual
Modbus Mappings
40046
40047
40048
40049
40050
40051
40052
40053
0x002D
0x002E
0x002F
0x0030
0x0031
0x0032
0x0033
0x0034
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
40054
40055
40056
40057
40058
40059
40060
40061
0x0035
0x0036
0x0037
0x0038
0x0039
0x003A
0x003B
0x003C
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
40062
40063
40064
40065
40066
40067
40068
40069
40070
40071
40072
40073
40074
40075
40076
40077
0x003D
0x003E
0x003F
0x0040
0x0041
0x0042
0x0043
0x0044
0x0045
0x0046
0x0047
0x0048
0x0049
0x004A
0x004B
0x004C
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
B-7
1=K Type
2=T Type
3=E Type
4=R Type
5=S Type
6=B Type
7=N Type
8=Voltage:78.126mV
9=Voltage:39.062mV
10=Voltage:19.532mV
CH1 TC Sensor Type
CH2 TC Sensor Type
CH3 TC Sensor Type
CH4 TC Sensor Type
CH5 TC Sensor Type
CH6 TC Sensor Type
CH7 TC Sensor Type
CH8 TC Sensor Type
20=AVG
21=DIF
Virtual CH9 TC Sensor Type
Virtual CH10 TC Sensor Type
Virtual CH11 TC Sensor Type
Virtual CH12 TC Sensor Type
Virtual CH13 TC Sensor Type
Virtual CH14 TC Sensor Type
Virtual CH15 TC Sensor Type
CH0 TC Reset Minimum Value
<R> Always 0
<W> 1=Reset, 0=return illegal data
value
CH1 TC Reset Minimum Value
CH2 TC Reset Minimum Value
CH3 TC Reset Minimum Value
CH4 TC Reset Minimum Value
CH5 TC Reset Minimum Value
CH6 TC Reset Minimum Value
CH7 TC Reset Minimum Value
Virtual CH8 TC Reset Minimum Value
Virtual CH9 TC Reset Minimum Value
Virtual CH10 TC Reset Minimum Value
Virtual CH11 TC Reset Minimum Value
Virtual CH12 TC Reset Minimum Value
Virtual CH13 TC Reset Minimum Value
Virtual CH14 TC Reset Minimum Value
Virtual CH15 TC Reset Minimum Value
CH0 TC Reset Maximum Value
<R> Always 0
<W> 1=Reset, 0=return illegal data
value
ioLogik E2262 User’s Manual
Modbus Mappings
40078
40079
40080
40081
40082
40083
40084
40085
40086
40087
40088
40089
40090
40091
40092
40093
0x004D
0x004E
0x004F
0x0050
0x0051
0x0052
0x0053
0x0054
0x0055
0x0056
0x0057
0x0058
0x0059
0x005A
0x005B
0x005C
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
40094
40095
40096
40097
0x005D
0x005E
0x005F
0x0060
1 word
1 word
1 word
1 word
40098
40099
40100
40101
0x0061
0x0062
0x0063
0x0064
1 word
1 word
1 word
1 word
40102
40103
40104
40105
0x0065
0x0066
0x0067
0x0068
1 word
1 word
1 word
1 word
40106
40107
40108
40109
0x0069
0x006A
0x006B
0x006C
1 word
1 word
1 word
1 word
40110
40111
40112
40113
0x006D
0x006E
0x006F
0x0070
1 word
1 word
1 word
1 word
40114
40115
40116
40117
0x0071
0x0072
0x0073
0x0074
1 word
1 word
1 word
1 word
40118
40119
40120
0x0075
0x0076
0x0077
1 word
1 word
1 word
B-8
CH1 TC Reset Maximum Value
CH2 TC Reset Maximum Value
CH3 TC Reset Maximum Value
CH4 TC Reset Maximum Value
CH5 TC Reset Maximum Value
CH6 TC Reset Maximum Value
CH7 TC Reset Maximum Value
Virtual CH8 TC Reset Maximum Value
Virtual CH9 TC Reset Maximum Value
Virtual CH10 TC Reset Maximum Value
Virtual CH11 TC Reset Maximum Value
Virtual CH12 TC Reset Maximum Value
Virtual CH13 TC Reset Maximum Value
Virtual CH14 TC Reset Maximum Value
Virtual CH15 TC Reset Maximum Value
CH0 DO Status
<RW> 0=OFF, 1=ON
CH1 DO Status
CH2 DO Status
CH3 DO Status
CH0 DO Power On Status
<RW> 0=OFF, 1=ON
CH1 DO Status
CH2 DO Status
CH3 DO Status
CH0 DO Safe Status
<RW> 0=OFF, 1=ON
CH1 DO Status
CH2 DO Status
CH3 DO Status
CH0 DO Pulse Output Status
<RW> 0=Stop, 1=Start
CH1 DO Pulse Output Status
CH2 DO Pulse Output Status
CH3 DO Pulse Output Status
CH0 DO Power On Pulse Output Status
<RW> 0=Stop, 1=Start
CH1 DO Pulse Output Status
CH2 DO Pulse Output Status
CH3 DO Pulse Output Status
CH0 DO Safe Pulse Output Status
<RW> 0=Stop, 1=Start
CH1 DO Pulse Output Status
CH2 DO Pulse Output Status
CH3 DO Pulse Output Status
CH0 TC Enable
<RW> 0 =Disable, 1=Enable
CH1 TC Enable
CH2 TC Enable
CH3 TC Enable
ioLogik E2262 User’s Manual
40121
40122
40123
40124
0x0078
0x0079
0x007A
0x007B
Modbus Mappings
1 word
1 word
1 word
1 word
CH4 TC Enable
CH5 TC Enable
CH6 TC Enable
CH7 TC Enable
5xxxx Write Registers (Function 8)
Sub-function
0x0001
0x0001
Data Field (Request)
0xFF00
0X55AA
Data Field (Response)
Echo Request Data
Echo Request Data
B-9
Description
Reboot
Reset with Factory default
C
Appendix C
Used Network Port Numbers
E2262 Network Port Usage
Port
68
68
69
80
161
502
4040
4800
9000
9000
Type
UDP
UDP
UDP
TCP
TCP
TCP
TCP
UDP
TCP
UDP
Usage
BOOTPC
DHCP
Export/Import File
Web Server
SNMP
Modbus Communication
ioEventLog
Auto Search
Active Message (Default)
Active Message (Default)
D
Appendix D
SNMP MIB II
RFC1213 MIB II Supported SNMP Variables
The following SNMP variables are built into the ioLogik firmware and are compliant with
RFC1213 MIB II.
System MIB
Interfaces MIB
IP MIB
ICMP MIB
SysDescr
ifNumber
ipForwarding
IcmpInMsgs
SysObjectID
ifIndex
ipDefaultTTL
IcmpInErrors
SysUpTime
ifDescr
ipInreceives
IcmpInDestUnreachs
SysContact
ifType
ipInHdrErrors
IcmpInTimeExcds
SysName
ifMtu
ipInAddrErrors
IcmpInParmProbs
SysLocation
ifSpeed
ipForwDatagrams
IcmpInSrcQuenchs
SysServices
ifPhysAddress
ipInUnknownProtos
IcmpInRedirects
ifAdminStatus
ipInDiscards
IcmpInEchos
ifOperStatus
ipInDelivers
IcmpInEchoReps
ifLastChange
ipOutRequests
IcmpInTimestamps
ifInOctets
ipOutDiscards
IcmpTimestampReps
ifInUcastPkts
ipOutNoRoutes
IcmpInAddrMasks
ifInNUcastPkts
ipReasmTimeout
IcmpOutMsgs
ifInDiscards
ipReasmReqds
IcmpOutErrors
ifInErrors
ipReasmOKs
IcmpOutDestUnreachs
ioLogik E2262 User’s Manual
System MIB
SysServices
Pinouts and Cable Wiring
Interfaces MIB
IP MIB
ICMP MIB
ifInUnknownProtos ipReasmFails
IcmpOutTimeExcds
ifOutOctets
ipFragOKs
IcmpOutParmProbs
ifOutUcastPkts
ipFragFails
IcmpOutSrcQuenchs
ifOutNUcastPkts
ipFragCreates
IcmpOutRedirects
ifOutDiscards
ipAdEntAddr
IcmpOutEchos
ifOutErrors
ipAdEntIfIndex
IcmpOutEchoReps
ifOutQLen
ipAdEntNetMask
IcmpOutTimestamps
ifSpecific
ipAdEntBcastAddr
IcmpOutTimestampReps
ipAdEntReasmMaxSize
IcmpOutAddrMasks
ipRouteDest
IcmpOutAddrMaskReps
ipRouteIfIndex
ipRouteMetric1
ipRouteMetric2
ipRouteMetric3
ipRouteMetric4
ipRouteNextHop
ipRouteType
ipRouteProto
ipRouteAge
ipRouteMask
ipRouteMetric5
ipRouteInfo
IpNetToMediaIfIndex
IpNetToMediaPhysAddress
IpNetToMediaNetAddress
IpNetToMediaType
IpRoutingDiscards
D-2
ioLogik E2262 User’s Manual
Pinouts and Cable Wiring
UDP MIB
TCP MIB
SNMP MIB
UdpInDatagrams
tcpRtoAlgorithm
snmpInPkts
UdpNoPorts
tcpRtoMin
snmpOutPkts
UdpInErrors
tcpRtoMax
snmpInBadVersions
UdpOutDatagrams
tcpMaxConn
snmpInBadCommunityNames
UdpLocalAddress
tcpActiveOpens
snmpInBadCommunityUses
UdpLocalPort
tcpPassiveOpens
snmpInASNParseErrs
tcpAttempFails
snmpInTooBigs
tcpEstabResets
snmpInNoSuchNames
Address Translation MIB
tcpCurrEstab
snmpInBadValues
AtIfIndex
tcpInSegs
snmpInReadOnlys
AtPhysAddress
tcpOutSegs
snmpInGenErrs
AtNetAddress
tcpRetransSegs
snmpInTotalReqVars
Address Translation MIB
AtNetAddress
TCP MIB
SNMP MIB
tcpConnState
snmpInTotalSetVars
tcpConnLocalAddress
snmpInGetRequests
tcpConnLocalPort
snmpInGetNexts
tcpConnRemAddress
snmpInSetRequests
tcpConnRemPort
snmpInGetResponses
tcpInErrs
snmpInTraps
tcpOutRsts
snmpOutTooBigs
snmpOutNoSuchNames
snmpOutBadValues
snmpOutGenErrs
snmpOutGetRequests
snmpOutGetNexts
snmpOutSetRequests
snmpOutGetResponses
snmpOutTraps
snmpEnableAuthenTraps
D-3
ioLogik E2262 User’s Manual
Pinouts and Cable Wiring
Private MIB File and SNMP Variables
Moxa also provides an SNMP to I/O MIB file that can help you monitor I/O status with SNMP
software. You can find the MIB file on the Document and Software CD.
Moxa-IO-MIB
totalChannelNumber
serverMode
systemTime
firmwareVersion
TC00-Index
TC00-Type
TC00-Range
TC00-Value
TC00-Min
TC00-Max
TC01-Index
TC01-Type
TC01-Range
TC01-Value
TC01-Min
TC01-Max
TC02-Index
TC02-Type
TC02-Range
TC02-Value
TC02-Min
TC02-Max
Moxa-IO-MIB
TC03-Index
TC03-Type
TC03-Range
TC03-Value
TC03-Min
TC03-Max
TC04-Index
TC04-Type
TC04-Range
TC04-Value
TC04-Min
TC04-Max
TC05-Index
TC05-Type
TC05-Range
TC05-Value
TC05-Min
TC05-Max
TC06Index
TC06-Type
TC06-Range
TC06-Value
TC06-Min
TC06-Max
D-4
Moxa-IO-MIB
TC07-Index
TC07-Type
TC07-Range
TC07-Value
TC07-Min
TC07-Max
DO00-Index
DO00-Type
DO00-Range
DO00-Value
DO01-Index
DO01-Type
DO01-Range
DO01-Value
DO02-Index
DO02-Type
DO02-Range
DO02-Value
DO03-Index
DO03-Type
DO03-Range
DO03-Value
E
Appendix E
Factory Default Settings
The ioLogik E2262 is configured with the following factory defaults:
Default IP Address:
Default Netmask:
Default Gateway:
Communication Watchdog:
Watchdog Timeout:
192.168.127.254
255.255.255.0
None
Disable
60 secs
TC Sensor Type:
TC Enable:
TC Unit Type:
K type
Enable
Celsius
DO Mode:
DO Safe Status:
Power On Status:
Low Width for Pulse:
Hi Width for Pulse:
DO
Off
Off
1 × 5 ms
1 × 5 ms
Output Pulses:
0 (continuous)
Password:
Module Name:
Module Location:
SNMP:
Community:
Contact:
Location:
NONE
NONE
NONE
Enable
Public
NONE
NONE
Click&Go
NONE
F
Appendix F
Pinouts and Cable Wiring
Ethernet Port Pinouts
Pin
Signal
1
Tx+
2
Tx-
3
Rx+
6
Rx-
1
8
Serial Port Pinouts
E2262 RS-485 Network Adapter Pin Assignment
Thermocouple Input Wiring
Structure
ioLogik E2262 User’s Manual
Pinouts and Cable Wiring
2-wire
Digital Output
Structure
Output Channel
* DO PWR is for powering up the field Power LED.
F-2
ioLogik E2262 User’s Manual
Pinouts and Cable Wiring
Terminal Block Pin Assignments
(TB1)
(TB2)
(RS-485)
7
8
9
10
11
12
13
14
15
16
TC2-
TC3+
TC3-
TC4+
TC4-
TC5+
TC5-
TC6+
TC6-
TC7+
TC7-
F-3
17
18
19
20
21
22
23 24
DO 3
6
DO 2
5
DO 1
4
DO 0
3
DO GND
2
6
SG
DO GND
1
TC2+
5
Data-
TC1-
4
Data+
TC1+
3
FG
TC0-
2
V-
TC0+
TB2
1
V+ (12-48V)
DO PWR
(Power Input)
TB1