6 Configuration of the transmitter 6.1 Change of adjusted range by entering numbers To change the transmitter’s adjusted range, perform the following operations: 1. 2. 3. 4. 5. If a transmitter was not found in the network, you must search for it. Go to Basic parameters tab. Adjust unit. Set start and end of the adjusted range. Permissible values are limited by the basic range and minimal range width. Save changes in a transmitter by clicking Enter. See also: Set range with assigned values. 6.2 Set range with assigned values This function is enabled by: Operations -> Basic functions -> Set range with assigned values -> Set range. Setting range adjusted with a set value (e.g. pressure) means saving a transmitter’s set value as start or end of adjusted range. Be careful not to exceed permissible range width. 1. Start After running the wizard, the main window is displayed. 41