1. Installation
Fieldbus cable
If the IP 65/IP 67 plugs from Festo are used, a cable outer
diameter of 7-10 mm is permissible. The following cable is
appropriate for use corresponding to the remote bus specifications:
Cable selection
Order no. Phoenix
3 x 2 x 0.22 mm2
IBS RBC METER-T (standard)
28 06 28 6
3 x 2 x 0.25 mm2
IBS RBC METER / F-T (highly flexible)
27 23 12 3
3 x 2 x 0.22 mm2
IBS RBC METER / E-T (can be laid
underground)
27 23 14 9
Procurement source:
Phoenix Contact GmbH & Co.
Postfach 1341
D-32819 Blomberg, Germany
www.phoenixcontact.com
Bus length
Specifications on the bus length can be found in the manuals
for your interface module.
Note
If the valve terminal is mounted into a moving part of a
machine, the fieldbus cable on the moving part must be
provided with strain relief. Also observe the corresponding
regulations in EN 60204 Part 1.
1.3.4
Fieldbus baud rate and fieldbus length
The maximum permissible fieldbus length is dependent on
the baud rate used. With a baud rate of 500 kBd, the maximum fieldbus length must not exceed 12.8 km (400 m per segment).
Festo P.BE-CPX-FB6-EN en 1207c
1-21