Download 80-NET
Transcript
Technical data UPS model Power kVA Temperature Maximum (8h) Transport and storage CHLORIDE 80-NET 60 80 80-NET 100 120 40 °C 160 200 -20 °C to +70 °C Max. relative humidity @ Up to 90% 20°C (non condensing) Max. altitude above sea-level Up to 1000 m above M.S.L. (at higher altitudes 80-NET without derating complies with IEC/EN 62040-3) Climate class Better than 3K2, see notes about installation site; check according to IEC 721 in accordance with IEC 68-2 Immunity to electrical interIEC 801/-2/-3/-4/-5/-6 ference EMC CLASS standard EN 50 091-2 Class RS 11.1.2. Input Nominal input voltage2) Input voltage range Min. voltage w/o battery discharge Mains configuration Nominal frequency Maximum input current @ ambient temp. 0°C to 40°C Power factor @ nominal load and input conditions3) 4) I/p current distortion @ nominal i/p conditions and max. i/p power4) 5) Maximum i/p current 400 V (3 Ph + N) 340 - 460 V 320 V Symmetrical 3Ph mains, e.g. TN-C, TN-S, TN-C-S 50 Hz (60 Hz selectable) ±6% 94 A 125 A 156 A 185 A 250 A 312 A ≥0.99 <3% <5% 4) 5) distortion Walk in/Soft start Rectifier Hold-off Inrush current/Imax. input6) 82 10 s (1-90 selectable) 1 s (1-180 selectable) ≤1 User Handbook 10H52167UM01 - Rev. 8 - 10/2008