Download MultiComm™
Transcript
3.4.3 RTH SUMMARY Data Registers for 2 ½ or 3 Element Mode (Cont’d) Quantity Holding Register Representation K-Factor Amps φA K-Factor Amps φB K-Factor Amps φC 40129 40130 40131 | | 100 = 1.00; 65535 = 655.35 | Set to 100 on low signal Displacement PF φA Displacement PF φB Displacement PF φC 40132 40133 40134 | 1047 = -1; 2047 = 0; 3047 = +1 | 4046 = Amps or Volts too low | (-) lagging; (+) leading Displacement PF Total 40135 1047 = -1; 2047 = 0; 3047 = +1 4046 = Amps or Volts too low (-) lagging; (+) leading Present Demand Fund. Amps N 40136 2047 = 0Amps; 4095 = 15.0*Amps Max Demand Fund. Amps N 40137 2047 = 0Amps; 4095 = 15.0*Amps Present Demand TDD1 Amps φA Present Demand TDD1 Amps φB Present Demand TDD1 Amps φC 40138 40139 40140 | | 0 = 0.0%; 9999 = 999.9% | Max Demand TDD1 Amps φA Max Demand TDD1 Amps φB Max Demand TDD1 Amps φC 40141 40142 40143 | | 0 = 0.0%; 9999 = 999.9% | Present Demand THD Volts φA Present Demand THD Volts φB Present Demand THD Volts φC 40144 40145 40146 | | 0 = 0.0%; 9999 = 999.9% | Max Demand THD Volts φA Max Demand THD Volts φB Max Demand THD Volts φC 40147 40148 40149 | | 0 = 0.0%; 9999 = 999.9% | * 1 - When CI1 Option (1Amp Input) is installed, divide this value by 5 If TDD Denominator is set to 2047 (0Amps) the TDD calculation will use Fundamental Amps as the Denominator, which will result in all Current Distortions being expressed as THD. ML0002 November 2009 13 Copyright 2009 Bitronics, LLC.