Download Model UP750 Program Controller User`s Manual for
Transcript
<Toc> 7-4 <7. Function Block Diagram and Descriptions> ■ Selecting Program Pattern Using Contact Input It is possible to select the program pattern by turning the four contact input signals ON or OFF. This function is assigned to DI1 (contact input 1) to DI4 (contact input 4). Note that the program pattern can be selected during RESET mode, can not during operation. Contact input Program pattern number to be selected (PT.No) 1 2 3 4 5 6 7 9 8 10 11 12 13 14 15 DI1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON DI2 OFF ON DI3 OFF OFF OFF ON DI4 OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF ON ON ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON For example, set contact input 2 (DI2) only to “ON” to change the program pattern 1 to the program pattern 2. Set contact input 1 (DI1) and contact input 2 (DI2) to “ON” to select the program pattern 3. ■ Switching Operation Mode Using Contact Input Program operation for the selected program pattern starts when DI5 (contact input 5) changes from OFF to ON. Program operation stops when DI6 (contact input 6) changes from OFF to ON. Preset output value is outputted when the operation stops. Local-mode operation starts when DI7 (contact input 7) changes from OFF to ON. Tracking switching function is assigned to DI7(contact input 7). Connect to contact output 3 (DO3) of the secondary-loop controller, since the cascade primary-loop control is used with the cascade secondary-loop control. If the operation of the secondary-loop controller changes from the cascade mode (to the manual or automatic mode), the primary-loop controller stops its control computation and outputs the input tracking signal as the manipulated output. When the secondary-loop controller changes to the cascade mode, the contact signal from the secondary-loop controller is turned off. And then, control computation restarts using the tracking signal that was input just before the cascade mode is established as the initial manipulated output value. Status of DI7 Output tracking operation ON Tracking input signal is output as manipulated output signal of the primary-loop controller. OFF Result of PID computation of the primary-loop controller is output. ■ PID It is possible to use a maximum of eight groups of PID parameters. Operating Parameters Function Parameter Main menu Submenu Proportional band (P) n.P LP1 n.PID Integral time (I) n.I LP1 n.PID Derivative time (D) n.D LP1 n.PID IM 05E01B02-42E 1st Edition : May 31,2000-00