Download PowerFlex 700 Adjustable Frequency AC Drive
Transcript
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6 Common Symptoms and Corrective Actions Drive does not Start from Start or Run Inputs wired to the terminal block. Cause(s) Indication Corrective Action Drive is Faulted Flashing red status light Clear fault. None Wire inputs correctly and/or install jumper. Incorrect digital input programming. None • Mutually exclusive choices have been made (i.e., Jog and Jog Forward). • 2 wire and 3 wire programming can be conflicting. • Exclusive functions (i.e, direction control) can have multiple inputs configured. • Stop is factory default and is not wired. Program [Digital Inx Sel], parameters 361…366 for correct inputs. Start or Run programming can be missing. Flashing yellow status light and “DigIn CflctB” indication on LCD HIM. [Drive Status 2] shows type 2 alarm(s). Program [Digital Inx Sel] to resolve conflicts. Remove multiple selections for the same function. Install stop button to apply a signal at stop terminal. Incorrect input wiring. Refer to the wiring examples starting on page 56. • • • • Press Stop Cycle power Set [Fault Clear] to 1 “Clear Faults” on the HIM Diagnostic menu. • 2 wire control requires Run, Run Forward, Run Reverse or Jog input. • 3 wire control requires Start and Stop inputs. • Jumper from terminal 25 to 26 is required. Drive does not Start from Human Interface Module (HIM). Cause(s) Indication Corrective Action Drive is programmed for 2 wire control. HIM Start button is disabled for 2 wire control unless param. 192, bit 1 = “1.” None If 2 wire control is required, no action needed. If 3 wire control is required, program [Digital Inx Sel] for correct inputs. Drive does not respond to changes in speed command. 74 Cause(s) Indication Corrective Action No value is coming from the source of the command. LCD HIM Status Line indicates “At Speed” and output is 0 Hz. 1. If the source is an analog input, check wiring and use a meter to check for presence of signal. 2. Check [Commanded Speed], parameter 002 for correct source. Incorrect reference source has been programmed. None 3. Check parameter 213, [Speed Ref Source] for the source of the speed reference. 4. Reprogram parameter 090, [Speed Ref A Sel] for correct source. Incorrect Reference source is being selected via remote device or digital inputs. None 5. Check parameter 209, [Drive Status 1], bits 12 & 13 for unexpected source selections. 6. Check parameter 216 [Dig In Status] to see if inputs are selecting an alternate source. 7. Reprogram digital inputs to correct “Speed Sel x” option. Rockwell Automation Publication 20B-IN019E-EN-P - July 2013