Installation 37
Procedure 12 - Connecting alarms on TB2
Step
Action
1
To access terminal block TB2 remove the section of the front panel
located below the LED display.
2
Insert the signal cable into the rectifier through the hole located on
the right side of the rectifier and run the connector to TB2 on the left
side.
end

Table 9 - Signals on terminal block TB2
Connection
Signal
TB2-1
EQL
Equalize signal from the controller
TB2-2
RG+
Remote sense ( + )
TB2-3
RC−
Remote sense ( – )
TB2-4
TR
TB2-5
HVSDR
TB2-6
HVSD
TB2-7
RFA ( NO )
Rectifier failure ( NO )
TB2-8
CURRENT SHARE
Forced current share
TB2-9
FAN ALM ( NC )
TB2-10
RFA ( C )
TB2-11
FAN ALM ( NO )
TB2-12
SH+
Output current shunt voltage ( + )
TB2-13
SH−
Output current shunt voltage ( – )
TB2-14
FAN ALM ( C )
TB2-15
RFA ( NC )
Rectifier failure alarm ( NC )
TB2-16
REF GRD
Battery and control reference ground
Emerson Energy Systems
Description
Temporary release from the controller
High voltage shutdown reset signal
from the controller
High voltage shutdown signal from the
controller
Fan alarm ( NC )
Rectifier failure alarm
Fan alarm ( NO )
Fan alarm ( common contact )
Rectifier 200/48NT5C05D User Manual