Download Helios Modular Switch Mode Rectifier 200/48
Transcript
Installation 37 Procedure 12 - Connecting alarms on TB2 Step Action 1 To access terminal block TB2 remove the section of the front panel located below the LED display. 2 Insert the signal cable into the rectifier through the hole located on the right side of the rectifier and run the connector to TB2 on the left side. end Table 9 - Signals on terminal block TB2 Connection Signal TB2-1 EQL Equalize signal from the controller TB2-2 RG+ Remote sense ( + ) TB2-3 RC− Remote sense ( – ) TB2-4 TR TB2-5 HVSDR TB2-6 HVSD TB2-7 RFA ( NO ) Rectifier failure ( NO ) TB2-8 CURRENT SHARE Forced current share TB2-9 FAN ALM ( NC ) TB2-10 RFA ( C ) TB2-11 FAN ALM ( NO ) TB2-12 SH+ Output current shunt voltage ( + ) TB2-13 SH− Output current shunt voltage ( – ) TB2-14 FAN ALM ( C ) TB2-15 RFA ( NC ) Rectifier failure alarm ( NC ) TB2-16 REF GRD Battery and control reference ground Emerson Energy Systems Description Temporary release from the controller High voltage shutdown reset signal from the controller High voltage shutdown signal from the controller Fan alarm ( NC ) Rectifier failure alarm Fan alarm ( NO ) Fan alarm ( common contact ) Rectifier 200/48NT5C05D User Manual