Chapter 1 Safety
Manual VIPA System SLIO
Functional safety - safety relevant parameters
General
This chapter describes characteristics associated to functional safety. In
according to IEC 61508 safety means that the residual error probability of
the whole system below the standard limits. In accordance to the whole
system internal safety-relevant device errors must be detected and be led
to a safe condition.
Safety relevant
parameters
The values here refer to the modules of this manual. Safety relevant
characteristics may always be found in the according manuals of the
modules.
Characteristics
SDI 4xDC 24V
Characteristics according
to IEC 61508
PFH = 0.25 * 10-9/h
PFDavg = 2.14 * 10-5
SFF according SIL 3
Probability of failure per Hour:
Probability of danger failure per hour.
Probability of Failure on Demand average:
Average of probability of failure on demand.
Safe Failure Fraction:
Fraction of failure, which lead to a safe state.
Characteristics according
to DIN EN ISO 13849-1
Meaning
MTTFd: high
Mean Time To dangerous Failure
DCavg: high
Diagnostic Coverage average
During the expected life of the device of up to
20 years, no proof test is required.
After this interval, the system SLIO safety
module must be decommissioned and sent
back to the vendor.
Device life: 20 Years