MOUNTING INSTRUCTIONS mains mains suppr. filter GEL 7925 7-3 7.2 EMC measures mains transformer Controller GEL 89033/ GEL 89036 GEL 8x10 mounting plate (conductive) control lines E180014I a) Mains suppression filter To achieve full functionality of the filter you must fix it to a bright and well earthed mounting plate, paying attention to having good contact at both sides. The screen (earth) is to be connected to the special labelled screw terminal on the filter. b) Mains transformer The transformer is to be fixed to the mounting plate, too. Contacting has to be performed with as large a surface area as possible (remove a possibly existing coat of lacquer). Additionally, earth the transformer via a short cable (≥ 2.5 mm2) to the mounting plate using the twin blade terminal (6.3 mm) on the transformer. Connect the mains earth wire resp. the screen of the mains cable coming from the filter to the ‘PE’ labelled terminal. Connect the screen of the Controller supply to the twin blade terminal on the transformer. c) Controller Each inserted module is earthed via a special contact socket in the upper metal angle (metal frame with devices) at the back of the Controller. Connect − the screen of the transformer cable (for devices without − the earth cable coming from the switch cabinet (door) to the twin blade connector on the metal angle/frame. certification) and Screen earthing is performed − by connecting the screens to the respective terminal strips or plugs of the individual modules (devices without certification, see appendix B) resp. − via the cable clips on the earthing angles screwed down on the metal frame (devices with certification, see figure on page 7-2). 8310/8610-8