CHV110 series energy saving cabinet
Functional
Reference
Functional
Reference
Set Value
Functional
Reference
Code
Set Value
P7.04
0
Code
Set Value
Code
P0.02
2
P0.09
P0.03
2
P0.11
0.7
P8.16
3
P0.04
1
P0.12
1.5
P8.18
1.0
9.3.4.2 Parameters for adjusting signal amplification rate are as follows:
Functional
Code
P5.25
P5.26
P5.27
P5.28
Functional
Function Description
Lower limit of channel 1
Setting
corresponding
P5.30
to
the lower limit of channel 1
Upper limit of channel 1
Setting
corresponding
Function Description
Code
P5.31
P5.32
to
the upper limit of channel 1
P5.33
Lower limit of channel 2
Setting corresponding to
the lower limit of channel 2
Upper limit of channel 2
Setting corresponding to
the upper limit of channel 2
When the energy saver runs in the mains supply mode, flow and pressure parameters
can be adjusted separately. Change P0.06 to be 0, observe flow parameters of channel
1, Which is compared with the analog frequency of the energy saver. If they are
inconsistent, adjust the parameters P5.25 to P5.28. After that, Change P0.06 to be 1,
observe pressure parameters of channel 2, Which is compared with the analog
frequency of the energy saver. If they are inconsistent adjust the parameters P5.30 to
P5.3.3. At last, Change P0.06 to be 3, which is the standard comparative input for two
channels.
9.3.4.3 During the use of the energy saver, if protection function is incorrectly enabled,
motor parameters may be incorrect. Change P0.00 to be 2 (V/F control) and try to
identify the cause.
9.3.4-4 Make sure the motor is in the stop state during the switchover between the mains
supply mode and energy saving mode; otherwise, the inverter will generate an OC fault.
9.3.4.5 Special treatment
If multi-step speed is required for the commissioning of some injection molding machines,
try the following methods:
Set the following parameters through the JOG terminal (S2):
Functional Code
Function Description
P5.03 (S2 terminal function selection)
4 (FWD JOG); 5 (REV JOG)
Set according to actual situations (less
P8.06 (JOG run frequency)
than the maximum frequency)
.115.