To change the desired minimum supply or discharge air temperature scroll through the SETPOINTS menu tree, locate the HTG MIN DA Setpoint, and enter a new temperature. This temperature must not be greater than the HTG MAX DA Setpoint. The allowable temperature range is 40°F - 130°F. This sets the lowest discharge air temperature that will leave the unit. To change the desired maximum supply or discharge air temperature scroll through the SETPOINTS menu tree, locate the HTG MAX DA Setpoint, and enter a new temperature. This temperature must not be less than the HTG MIN DA Setpoint. The allowable temperature range is 40°F - 130°F. This sets the highest discharge air temperature that will leave the unit. If the maximum and minimum discharge temperature setpoints are set for the same temperature, the supply air temperature will be the same as the setpoint regardless of the room temperature setpoint or actual room temperature. Recirculating Direct-Fired Heaters Using different controller software, the AireLogic DDC system can accommodate three distinct types of recirculating direct-fired units: those that return air before the burner and employ a special airflow station, those that return air before the burner and do not employ a special airflow station, and those that recirculate air after the burner. Recirculating direct-fired units, like all direct-fired units, deliver all of their products of combustion directly to the heated air space. For this reason it is extremely important that the proper ventilation rate be maintained to dilute these emissions. AireLogic units, that recirculate air before the burner and employ an airflow measuring station, utilize a control scheme that measures air pressure to determine the ratio of outside air and return air. These units are listed by an independent third party testing agency and use the equivalent temperature rise control scheme to limit burner modulation. The AireLogic system accurately measures the ratio of outside and return air, calculates the allowable equivalent temperature rise and automatically limits the burners firing rate. This insures the products of combustion, delivered to the space by the unit, are held at or below allowable OSHA thresholds. The outside air percentage is the driving parameter for this function. A greater percentage of outside air or dilution air enables the unit to generate a higher allowable equivalent temperature rise. The maximum allowable equivalent temperature rise for 20% outside air is 48.9°F. The maximum allowable equivalent temperature rise increases 1.22°F for each 1% increase in outside air. AireLogic units, that recirculate air before the burner and do not employ an airflow measuring station, utilize a control scheme that measures damper position to determine the percentage of return air. These units are not listed by an independent third party testing agency but do use the equivalent temperature rise control scheme to limit burner modulation. The maximum allowable equivalent temperature rise for 20% outside air is 48.9°F. The maximum allowable equivalent temperature rise increases 1.22°F for each 1% increase in outside air. For AireLogic units that recirculate air before the burner and use the MDT or MDT-Expert control, the maximum burner firing rate is limited by the discharge setpoint or the maximum allowable equivalent temperature rise whichever is less. 20