Download Instruction Manual

Transcript
F1000-G
control except auto circulating running.
・This function can alleviate the current impact during direction switch process, with
manufacturer’s setting value at 0S.
F121
Stop Mode
Setting Range: 0: Stop at Deceleration Time
1: Free Stop
Mfr’s Value:0
・“Free Stop” means that motor will have free running with an immediate output cutoff
and stop by friction upon receiving the “stop” command.
・This function can be used for “stop” operation in mode of keypad control and
interrupting direction signal operation in mode of terminal control.
F123 Jogging Function
Setting Range:0:Invalid jogging function 1:Valid jogging function
F124 Jogging Frequency (Hz)
Setting Range: F112~F111
F125 Jogging AccelerationTime(S)
F126 Jogging DecelerationTime(S)
Mfr’s Value: 0.4~3.7KW:5.0S
5.5~30KW:30.0S
37~400KW:60.0S
Setting Range:
0.1~3000
・It includes keypad jogging and terminal jogging.
f
Receivingjogging
operation command
terminal jogging works both in run and stop states.
・Jogging operation on the keypad (in stop state):
a.
Press “Mode” key to display “HF-0”, and
Jogging Operation
Cancel jogging
operation command
Keypad jogging is only valid in stop state while
Mfr’s Value: 1
Mfr’s Value: 5.00Hz
t
press “Set” to confirm showing “0”.
b.
Press “Run”, and inverter will run to “Jogging
Fig 5-1
Jogging Operation
Frequency” (“Keypad Jogging” will be canceled by pressing “Mode” again).
・In case of terminal jogging, make “Jogging” terminal (like OP1) connected to CM, and
inverter will run to the jogging frequency.
Note1
・“Stalling Adjusting” and F120 is invalid in mode of jogging operation.
F127/F129
Skip Frequency A, B (Hz)
Setting Range: 0~400.0
Mfr’s Value: 0Hz
F128/F130
Skip Area A, B (Hz)
Setting Range:±2.5
Mfr’s Value: 0.5
・System resonance will occur around a certain frequency point during motor running. This
parameter is set specifically to avoid resonance.
・ When output frequency reachs the setting value of this parameter, inverter will
automatically run by tripping off this “Skip Frequency”.
·17·