Chapter 4 Software Index
0- Drive Operation Mode
Function
Code No.
LCD Display
0-00
(Control Mode)
0-01
0-02
0-03
(Motor Rated Volt)
(Motor Rated Amp)
(Motor Rated KW)
(Motor Rated RPM)
Description
Range/Code
Control Mode
0-05
(Motor Rated Hz)
Motor Rated Voltage (Vac)
Motor Rated Current (Amp)
Motor Rated Power (kW)
Motor Rated Speed
(RPM)X100*7
Motor Rated Frequency (Hz)
0-06
(Auto Tuning)
Motor Parameter Auto Tuning
0-07
(AC Input Volt)
AC Line Input Voltage (Vac)
0-04
0-08
(Select Language)
Language Selection
0000: Vector (General Purpose)
0001: Vector (Variable Torque)
0002: Volts/Hz (Refer to Parameter
Group 10- Volts/Hz Mode)
-------------
Factory
Remarks
Setting
0000
*3*5
*3*5
*3*5
*3*5
--------0000: Invalid
0001: Valid
220V SERIES:170.0~264.0
440V SERIES:323.0~528.0
0000: English
0001: German
0002: French
0003: Italian
0004: Spanish
*3
*3*5
0000
*3
0000
Only for
LCD
keypad
1- Start/Stop and Frequency Control Modes
Function
Code No.
1-00
1-01
LCD Display
(Run Source)
Description
Range/Code
Run Command Source Selection
Run/Stop-Forward/Reverse
(MFIT Run Mode) Operation Mode with External
Terminals
1-02
(Reverse Oper)
Prohibition of Reverse operation
1-03
(Keypad Stop)
Keypad Stop Button
1-04
(Starting Method)
1-05
(Stopping Method) Stopping Method Selection
Starting Method Selection
4-10
0000: Keypad
0001: External Run/Stop Control
(See 1-01)
0002: Communication
0003: Built-In PLC
0000: Forward/Stop-Reverse/Stop
0001: Run/Stop-Forward/Reverse
0002: 3-Wire Control ModeRun/Stop
0000: Enable Reverse Command
0001: Disable Reverse Command
0000: Stop Button Enabled
0001: Stop Button Disabled
0000: Normal Start
0001: Enable Speed Search
0000: Controlled Deceleration-toStop with DC Injection
Braking (Rapid Stop)
0001: Free run Stop
Factory
Setting
0000
0000
0000
0000
0000
Remarks