Download Instrumentation Temperature Controller Instruction Manual
Transcript
1.2 Product Numbers and Specifications Product Numbers: ITC10X X corresponding to 399 for 0°C to 399°C range 999 for 0°C to 999°C range Example: ITC10399: ITC, 1000 watts maximum heater power, 0°C to 399°C range Sensor Requirement Thermocouple; Type K Range 0° to 390°C, or 0° to 999°C, as ordered Absolute Accuracy ±.5% of full scale Repeatability .5°C at constant ambient Sensititivity to Ambient Changes .05°C per °C change Operating Ambient 10° to 50°C Switched AC Power 1000 watts; zero-crossing error: 5V AC max. Proportioning Bandwidth ±3°C Proportioning Frequency 2 Hz Setpoint 1° C increments; push button selection Max. Power Input Requirement 10.0 amps at 117 VAC Power Attenuation 0 to 90% in 10% increments Physical Dimensions 2.4" x 8.3" x 5.9"; weight 1 lb. 14.4 oz. Visual Indicators • Power On (PWR) - illuminated whenever the instrument is plugged into a source of 120V AC, and the PWR switch is in the ON position • H ea t er O n (HT R ) - i l lu mi nat ed w henever t he cont rol ler a ppl ies power to the heater • Thermocouple Fault (TCPL) - illuminates whenever thermocouple sensor opens. (If a sensor failure is detected, heater power is automatically interrupted, and the HTR indicator will remain OFF.) 3