Adding Redundancy with Redundant I/O Modules
SS Status (Slave Scanner – DF108)
iored.ssXStatus
BIT
Value
0
Current in PWR1
(current of power supply 1)
0: Bad - 1: Good
1
Current in PWR2
(current of power supply 2)
0: Bad - 1: Good
2
Voltage 1
(voltage of power supply 1)
0: Bad - 1: Good
3
Voltage 2
(voltage of power supply 2)
0: Bad - 1: Good
4
Partner SS
(communication with partner slave scanner)
5
reserved
6
reserved
0: Bad - 1: Good
7
Module
(module general status)
0: Bad - 1: Good
0: Bad - 1: Good
Table 3 – SS Status
I/O Module Status
iored.moduleXXYstatus
BIT
Value
0
HS_PWR_0_5V
(internal voltage of HS board)
0: Bad - 1: Good
1
HS_PWR_1_5V
(internal voltage of HS board)
0: Bad - 1: Good
2
LS_INT_VCC
(internal voltage of LS board)
0: Bad - 1: Good
3
LS_EXT_VCC
(external voltage of LS board)
0: Bad - 1: Good
4
LS_ACTIVE_IDLE_FAIL_Status_b0
(internal status of LS board)
5
LS_ACTIVE_IDLE_FAIL_Status_b1
(internal status of LS board)
00: FAIL
01: ACT
10: IDLE
11: FAIL
6
IO_STATUS
0: Bad - 1: Good
7
Module_Status
(module general status)
0: Bad - 1: Good
Table 4 – Module Status
Value
255
Point Status
iored.pairXX.pointYY
GOOD
Valid for all modules
(point status indicates good conditions)
1
Error Max Positive
(maximum positive error)
Valid for Analog modules
2
Error Max Negative
(maximum negative error)
Valid for Analog modules
3
Error
(status of point with error)
Valid for Digital modules
Table 5 – Point Status