Actions box 212 Check the Boulter Buderus 24V AC external 3-way valve – activation (1) A CAUTION! To prevent damage, do not insert the measuring electrodes of the multimeter too far into the holes of the plug-and-socket connection. z Take the boiler out of operation, see box 43, 44 or 47. 7 box 216 z Insert the power supply plug of the Boulter Buderus 24V AC external 3-way valve. z Put the boiler into operation, see box 51, 54 or 55. box 217 Replace the Boulter Buderus 24V AC external 3-way valve – servomotor z Take the boiler out of operation, see box 43, 44 or 47. box 213 z Remove the power supply plug of the servomotor of the Boulter Buderus 24V AC external 3-way valve, see box 213. box 218 z Remove the power supply plug of the servomotor of the Boulter Buderus 24V AC external 3-way valve. box 214 z Put the boiler into operation, see box 51, 54 or 55. box 215 z Remove the servomotor of the Boulter Buderus 24V AC external 3-way valve. To release the servomotor press the release catch (item 1) and twist the servomotor. A 6 3 2 Plug-in contacts of Boulter Buderus 24V AC external 3-way valve Purpose Plug-in contacts on DBA control panel 2 24V AC 5 3 0V AC 6 6 _ \ __ 7 DANGER OF DAMAGE TO THE SYSTEM! Before removing the servomotor, check to see if the Boulter Buderus 24V AC external 3-way valve is in its "heating mode" position, and wait for the boiler display code C [0h] to appear. This prevents sudden pressure surges occurring in the heating circuit while the removal operation is taking place, and the resultant accidental opening of the pressure relief valve. box 219 z Fit the new servomotor by following the above procedure in reverse order. z Put the boiler into operation, see box 51, 54 or 55. z Set the multimeter to “measure AC voltage”. Minimum measuring range: 40V AC. z Open a hot water tap. z Adjust the hot water in the "Settings" menu on the DBA control panel of the boiler to 60 °C, see box 61. z Check to see if, during operating code C [0c], 24 V AC is detected at plug-in contacts “2” and “6”. z Close the hot water tap. z Check to see if, during operating code C [0h] , 24 V AC is detected at plug-in contacts “2” and “3”. We reserve the right to make technical modifications Boulter Buderus Ltd • http://www.boulter-buderus.co.uk Servicing manual Gas condensing boiler Buderus 500-24/S, 500-24/C and 500-28/C • Issued 02/2005 63