5.6.
Cable Cross-sections
SANTERNO PPC 15 Cabinet
2
X1: N. 2 terminals for 0.5...4mm flex cable
2
X2: N. 10 terminals for 0.5...2.5mm flex cable
2
X3: N. 34 terminals for 0.5...2.5mm flex cable
2
X4: N. 2 terminals for 0.5...4mm flex cable
SANTERNO PPC 180 Cabinet
X1: N. 2 terminals for 0.5...4mm2 flex cable
2
X3: N. 65 terminals for 0.5...2.5mm flex cable
2
X4: N. 2 terminals for 0.5...4mm flex cable
5.7.
Terminal Functions for SANTERNO PPC 15
The terminal lists given in this section describe the full functionality of the Power Plant Controller. Check
the optionals fitted in the substation and the relevant connections.
Terminal board X1 is for the connection of the supply voltage to the cabinet.
X1
Line Input Terminals
Terminal
Description
1
230Vac 50Hz Line input
2
Neutral
Potential
L
N
Terminal X2 is for the power supply of the CTs, the VTs and the Power Meter
X2
CTs, VTs and Power Meter
Terminal
Description
1
Voltage transformer L1
2
Voltage transformer L2
3
Voltage transformer L3
Neutral of the star centre of the Voltage transformer L1, L2 and
4
L3
5
Current transformer secondary S1 phase L1
6
Current transformer secondary S2 phase L1
7
Current transformer secondary S1 phase L2
8
Current transformer secondary S2 phase L2
9
Current transformer secondary S1 phase L3
10
Current transformer secondary S2 phase L3