Download User manual
Transcript
μC3 1. Introduction 1.1 General description The μC³ is a new compact CAREL electronic controller, measuring the size of a normal thermostat, for the complete management of chillers and heat pumps: it can control air-air, air-water, water-water and condensing units. Main functions • Temperature control for air/air units, air/water-cooled chillers/heat pumps, with two circuits and up to 6 steps, with and without reversal on the water/refrigerant circuit; • condenser control in two circuits with up to 6 steps on air/water-cooled units, with and without reversal on the water/refrigerant circuit; • defrost management by time and/or by temperature or pressure; • fan speed control; • complete alarm management; • time band management; Advanced functions • sliding defrost • functions to prevent high condensing pressure/temperature, low evaporator pressure/temperature, antifreeze • control • management of tandem, trio and semi-hermetic compressors • pump-down • part-winding start Driver functions • Electronic expansion valve management. Devices controlled • Compressor; • condenser fans; • evaporator fan (air-source units) • reversing valve; • water pumps for the evaporator and/or condenser (water-source units); • outlet fan (air-air); • antifreeze heater; • support heaters; • alarm signal device; Programming CAREL offers the possibility to configure all the unit parameters not only from the keypad on the front panel, but also using a hardware key or via a serial line. 1.2 User interface pLD large terminal The display has 4 digits plus decimal point. In normal operation, the value shown on the display corresponds to the temperature read by the control probe, for example the evaporator water inlet temperature (on water chillers) or alternatively the room temperature, on direct expansion units. Prg button: enters the parameters menu; if already in the menu goes back one level at a time until reaching the main screen Amber LED On = parameters menu Off = other menu Up button: enters the passwordprotected menu and scrolls the parameters Amber LED On = pump on Off = pump off Flashing = pump alarm Heat button: enters the parameters menu; if already in the menu goes back one level at a time until reaching the main screen Green LED On = parameters menu Off = other menu Alarm button: displays the alarm menu Red LED On = alarm active Off = no alarm On/off button: switches the unit on/off Red LED On = unit on Off = unit off Cool button: activates HP mode Green LED On = HP mode Off = chiller mode Sel button: selects the chosen parameter and confirms the changes Green LED On = main menu Off = other menu Down button: enters the password-protected menu and scrolls the parameters Green LED On = compressors on Off = compressors off Flashing = compressor alarm Fig. 1.a +030220431 rel 1.5 16/11/2009 5