Operation ER Code 05 Alarm Compressor run time Floating contact - Causes • • • • 06 Make-up time - Set value exceeded. Severe water loss in the system. Air lines leaking. Solenoid valve in the overflow line does not close. • • 07 Make-up cycles - 08 Pressure measurement YES • • • • Set value exceeded. Water loss in the system. • Make-up line not connected. • Make-up rate insufficient. • Make-up hysteresis too low. Set value exceeded. • • Controller receives incorrect signal. • • • • • • • 09 10 Level sensor Maximum pressure YES - Controller receives incorrect signal. • • • 11 Make-up quantity - Set value exceeded. Overflow line disabled. Dirt trap clogged. "With water meter" must be activated in the Customer menu. • Set value exceeded. • Severe water loss in the system. • • • • • • • • Remedy Alarm reset Check set value in the Customer or Service menu. Check the water loss and correct, if necessary. Seal any leak in the air system. Check functioning of the "PV1" solenoid valve. Check set value in the Customer or Service menu. Check water level. Connect make-up line - Check set value in the Customer or Service menu. Seal any leak in the system. Connect the plug. Check functioning of the pressure sensor. Check the cable for damage. Check the pressure transducer. Check functioning of the oil pick-up sensor. Check the cable for damage. Connect the plug. Check set value in the Customer or Service menu. Check functioning of the overflow line. Clean the dirt trap. Check set value in the Customer or Service menu. Check water loss in the system and repair, if necessary. Reflexomat with Basic controller — 13.05.2014 "Quit" "Quit" "Quit" "Quit" "Quit" "Quit" English — 51