Download XM-360 Process Module User Guide
Transcript
24 Installing the XM-360 Process Module A single switch contact can also be shared by multiple XM-360 modules wired in series as shown in Figure 2.12. When multiple modules are wired to a single switch, only one 4-20mA output channel is necessary to supply all the modules. ATTENTION IMPORTANT TIP The relay reset connections may be different for different XM modules. Figure 2.12 applies only to the XM-360 module. Refer to the installation instructions for the module for its terminal assignments. The XM-360/361/362 relay reset signal is not compatible with other XM module’s relay reset input. Use of a single switch requires a multi-pole switch. Refer to the XM Module User Manual for more information about the other XM modules. Up to 24 XM-360 modules can be wired in series in a single loop. Figure 2.12 Typical Multiple XM Modules Remote Relay Reset Signal Connection Publication GMSI10-UM006C-EN-P - August 2010