CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Description / Notes
Note that there is always a dead zone at the starting of
the curve where the frequency reference remains at
the value of the minimum frequency (P133), even when
the input signal is changed. This dead zone is only
suppressed when P133 = 0.0.
The internal value AI1' that defines the frequency
reference to be used by the inverter, is given as percent
of the full scale reading and is obtained by using one
of the following equations (see P235):
P235
Signal
0
0 to 10 V
0
0 to 20 mA
1
4 to 20 mA
Equation
( AIx10. GAIN + OFFSET
100
AIx . GAIN
OFFSET
AI1' = (
+
20
100
(AIx - 4)
OFFSET
. GAIN +
AI1' = (
16
100
AI1' =
Table 6.10 b) - Analog input signal AI1 (P235) definition
Where:
- AI1 is given in V or mA, according to the used signal
(see parameter P235);
- GAIN is defined by the parameter P234;
- OFFSET is defined by the parameter P236.
This is shown in the block diagram below:
P234
AI1
P235
GAIN
AI1'
OFFSET (P236)
Figure 6.18 b) - Block diagram of the analog input A1
Following situation as example: AI1 is the voltage
input (0-10 V - P235 = 0), AI1 = 5 V, P234 = 1.00
and P236 = -70 %.
Thus:
(-70)
5 .
1.00 +
AI1' =
= -20 %
10
100
[
The motor will run in reverse direction of rotation as
defined by the commands (negative value) - if this is
possible (P231 = 2), with a module reference equal to
0.2 or 20 % of the maximum output frequency (P134).
I.e., if P134 = 66.0 Hz, then the frequency reference is
equal to 13.2 Hz.
77