Download Softstarters Type PSE18...PSE370 Installation and
Transcript
5:2.5.5 Analog output, terminals 13 and 14 Analog output can be used for the connection of analog instruments. If the analog output is used, the cables shall be connected to terminals 12 (+) and 13 (-). See figures 5.14 and 5.15. Analog out signal can vary in the range 4 - 20 mA, corresponding to 0 - 120 percent of set value for parameter Ie. 100 percent corresponds to 17.3 mA. Warning! Do not connect an external voltage to any of the control terminals 8, 9, 10, 11, 12 and 13. Failure to observe the above may damage the softstarter and the warranty may no longer be valid. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 PSE 18-600-70 Figure 5.14: Terminals for analog output 1 2 3 4 5 6 7 8 9 10 11 12 13 14 M3 3,5 x 0,6 mm (0.138 x 0.024 in) 0,5 Nm - 4,3 lb.in Figure 5.15: Tightening torques and wire area 40 Chapter 5 Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201 AWG 24 ... 12 0,2 .. 2,5 mm2 2x0,2 .. 1,5 mm2 0,2 .. 2,5 mm2 2x0,2 .. 1,5 mm2