LYTEMODE INPUT M ODULE - ILSCLIM
Product
Specifications
ILSCLIM
LYTEMODE INPUT M ODULE
FOR USE WITH ILSCL2RES, ILSCL6RES, ILSCL8RES,
ILSCL6MMES & ILSCL8RSPS
Project:
Location/Type:
Description
The ILSCLIM is an add-on module that allows up to 8 momentary dry contact inputs to control any of the LYTEmode 2, 6, or 8 button remotes, Mini-Master, or Room Combine. The
ILSCLIM is designed to combine with the button station and fit in a 2-gang box.
Features
• Provides up to 8 momentary dry contact inputs for control of any LYTEmode 2, 6, or 8
button station.
• No additional button station programming required.
• Combines with the button station in a standard 2-gang box.
• Easy installation.
Note: Shown without Compli Faceplate. 2-gang Compli
Faceplate included. Single gang: 2.75" x 4.5" O.D.
Application
The ILSCLIM contains a 10-pin connector that will interface with the button station. Each
Input is designed to receive a momentary dry contact closure between the Input (pins 1-8)
and Ground (pins 9 and 10). When added to a button station, the inputs will control the following buttons:
INPUT
2 Button
6 Button
8 Button
1
ON
ON
E
2
A
F
3
B
G
4
C
H
5
D
I
OFF
J
7
RAISE
K
8
LOWER
L
6
Made in U.S.A.
ILSCLIM
OFF
9
GND
GND
GND
10
GND
GND
GND
ILSCL2RES - Two Button Remote:
Works with V1.03 and greater. Only Inputs 1 and 6 are valid.
ILSCL6RES - Six Button Remote:
Generates scenes ON, A-D, OFF, Raise and Lower.
ILSCL8RES - Eight Button Remote:
Generates scenes E-L.
ILSCL6MMES - Mini-Master (see User Manual for Mode Settings):
Mode 0 - Generates scenes ON, A-D, OFF, Raise and Lower.
Mode 1 - Generates scenes E-I, OFF, Raise and Lower.
Mode 2 - Generates scenes ON, A-D, OFF, Raise and Lower.
When Inputs 1 and 2, or 1 and 3, or 1 and 4, or 1 and 5 are
closed at the same time extended scenes E-H will be generated.
When Inputs 6 and 2, or 6 and 3, or 6 and 4, or 6 and 5 are
closed at the same time, extended scenes I-L will be generated.
Mode 3 - Input 5 is Remote Lock, Input 6 is Panel Lock, Input 7
is Cinema Cycle, and Input 8 is Alarm.
ILSCL8RSPS - Room Combine:
Controls Partition buttons E-L. Open to Close transition will combine two rooms (Button LED On). Close to Open transition will uncombine two rooms (button LED Off). Button can always override
the Inputs (last action).
For technical/sales assistance, call: 1-800-526-2731
www.philipslightingcontrols.com P/N 87-0510
LYTEMODE INPUT M ODULE - ILSCLIM
Specifications
Product
Specifications
Dimensions
The ILSCLIM shall provide eight (8) momentary dry contact inputs to control of any of the
LYTEmode 2, 6, or 8 button remotes, Mini-Master, or Room Combine. No additional programming of the button station shall be required. The ILSCLIM shall connect to the button station using a 10-wire ribbon cable (supplied) and shall fit in a standard 2-gang box when combined.
1 IN 1
2 IN 2
3 IN 3
4 IN 4
5 IN 5
6 IN 6
7 IN 7
8 IN 8
9 GND
10 GND
Input Limits
Closed:
0.0Vdc to 1.5Vdc
Opened: 2.5Vdc to 24Vdc
Current: 2mA to Ground
Note: Inputs are internally pulled to 5.0V
CAUTION: Input must never be pulled below ground.
DRY CONTACT INPUT S
1.7 inches
2.7 inches
Depth: 1.4 inches (occupies one standard gang)
Typical Wiring Diagram
Dry Contact Inputs
1 IN 1
2 IN 2
3 IN 3
4 IN 4
5 IN 5
6 IN 6
7 IN 7
8 IN 8
9 GND
10 GND
LYTEMODE MINI-MASTER/REMOTE
10-Wire Ribbon Cable
(supplied)
ILS NETWORK
Connect a wire from GND to
Ground or Common on input
device. This may be required
on each input circuit depending on source type.
DRY CONTACT INPUT S
LYTEMODE ILSCLIM
BR
W H/BR
BL
W H/BL
GN
W H/GN
SHLD
OR
W H/OR
9
8
7
6
5
4
3
2
1
ILS Network
Pin 9: GND (BR)
Pin 8: +24V (WH/BR)
Pin 7: GND (BL)
Pin 6: +24V (WH/BL)
Pin 5: GND (GN)
Pin 4: +24V (WH/GN)
Pin 3: Shield
Pin 2: Data- (OR)
Pin 1: Data+ (WH/OR)
REAR VIEW