Download POWER QUALITY ANALYSIS - Electri-Temp
Transcript
Ordering information Power Quality Analysis - Instrument MI 2292 PQA Plus or MI 2092 PHA - Current clamp 1000 A/1V, 3 pcs - Small soft carrying bag for current clamps - Test tip, red; 3 pcs - Safety flat clamps, 4 pcs - Alligator clip, black; 4pcs - Voltage measurement cables; 6 pcs - Mains cable - RS 232 cable - 4 × 1,2 V NiMH batteries - Power Link PC analysis and control SW package - Soft carrying bag - Instruction manual - Handbook "Modern Power Quality Measurement Techniques" on CD - Product verification data Standard Set Part No. MI 2092 - Standard Set Part No. MI 2292 (with safety flat clamps S 2015) Power Harmonics Analyser Power Quality Analyser Plus Power Quality Analyser Plus MI 2292 Power Harmonics Analyser MI 2092 • Metrel´s top of the range three- phase, multifunction power quality analyser with a complete selection of test functions and diagnostic tools for wide range of applications. • Automatic EN 50160 power quality assessment test. • Flicker measurement in accordance with EN 50160. • Modem communication support for remote control of the instrument. • Measurements according to IEC / EN 61000-4-30. • Recording of short-period events like transients, inrush currents, resonant states, switchings, etc. • Harmonics direction determination. • Optional: 110 V version. • Three-phase, multifunction power quality analyser suitable for performing all the most frequent measurements and diagnostics in different electrical systems. • Optional remote modem communication support. • Optional: 110 V version. Optional accessories Energy Measurement Active & Reactive Import & Export Inductive & Capacitive. Separate registers for Total, Sub-total & Last Integration Period Voltage and Current Harmonic Analysis up to 63rd component True Real Time operation for voltage interrupts and power break capturing 2 MB of memory allow data logging up to several months. A 1100 A 1120 Modem Remote Control by using GSM or standard type of telephone communication. Waveform analysis Scope function allows monitoring of current and voltage Configuration menu for setting the measuring method, integration period, current scaling factor and selection of signals. Technical specification AC VOLTAGES Three-phase AC voltage input (3 differential inputs, L1 - N1, L2 - N2, L3 - N3) Input voltage range: 10–550 Vrms L-N, 900 Vrms L-L 600 Vrms L-N (overload 10 s) Optional on request: 10–750 Vrms L-N, 1000 Vrms L-L 800 Vrms L-N (overload 10 s) Resolution: 0.1 V Accuracy: ± 0.5 % of reading ± 2 digits Crest factor max.: 1...1.4 @ 550 Vrms L-N Frequency range: 43–68 Hz fundamental AC CURRENTS Three-phase AC input for connection to current transducers with voltage output Input current (voltage range): 0.02–1 Vrms (from 0.02 x In to In) input Resolution: 0.3 mV (0.3 A with 1000 A / 1 V) Accuracy: ± 0.5 % of reading ± 6 digits plus current transformer accuracy Crest factor: 1...2.5 @ 1 VRMS Maximum permissible overload: 150 % In (sinusoidal current) Maximum input voltage: 1 Vrms PHASE ANGLE Consider phase angle data of current transformer used. SCOPE Display options: Waveform of pairs (L1: U1 and I1, L2: U2 and I2, L3: U3 and I3), U1, 2, 3, and I1, 2, 3 Ranging: Auto / manual A 1099 A 1037 A 1039 6 Part No. MI 2292 Standard Set METER – Power measurement Quantities related to selected measuring connections per phase, i.e.: Measured: voltage (U), current (I), cosj between U and I Calculated: active power (P), apparent power (S), reactive power (Q), power factor (Pf) with its characteristics (c, I, none) Line – Line voltage; Quantities for complete three-phase system, i.e.: Calculated: active power (Pt), apparent power (St), reactive power (Qt), power factor (Pft), neutral current (In); Basic accuracy for P, Q, S,: ± 1 % of reading Resolution for P, Q, S,: 0.01 of displayed value SPECTRUM – Harmonics measurement The instrument computes harmonics on signals sampled with an A/D converter. Recording interval: 160 ms (8 cycles) Spectrum calculation range: DC – 63rd Spectrum display range: DC – 25th Displayed items for selected harmonic: Order, relative and absolute value Range Limits of error Resolution Irange Urange THD Total Harmonic HD Harmonic on LCD and PC Distortion Distortion 2 … 100 % 0.2 % x Ur/U (Ir/I ) 0.2 % x Ur/U (Ir/I) 0.1 % ENERGY Displayed quantities from integration of calculated power as: – cumulative values (TOTAL); – partly cumulative (resettable by user request) (SUBTOTAL); – values related to last integration period (LAST IP). Quantities. Active energy (EP), capacitive energy (EQC), inductive energy (EQI) Basic accuracy: ± 1 % of reading Resolution: 0.1 of displayed value RECORDER Periodics integration period: 1 s – 900 s Selected signals: max. 64 Statistics values: each period divided in 200 parts (0.1 ms) Voltage anomalies: based on half period, start, duration and extremes of voltage EN 50160 ANALYSIS MODE (MI 2292 and MI 2192) Voltage dips, swells, sags and breaks, resolution 10 ms, no gaps Voltage unsimetry, Voltage RMS values, Frequency Harmonics: up to 43rd component Flickers Plt Pst: no gap FLICKER MEASUREMENT The instrument computes flickers according to IEC 61000-4-15 (MI 2292 only) WAVEFORMS Sampling rate: 128 scans / period (MI 2292 - 7812 periods, MI 2192 - 390 periods) Trigger: level, manual, timer Buffer: min. 10 periods of pre / post size, up to 7812 periods can be recorded Channels: 3 x U, 3 X I, U lines, Min / Max rms values: Avg Pf, cosj, Crest factor, THD U, I Frequency Harmonics / direction: magnitudes / positive / negative FAST LOGGING Sampling rate: 128 scans / period, min, max, avg recorded each half period Trigger: level, manual, timer Buffer: pre / post size, up to 166 minutes of recording Channels: 3 x U, 3 X I, Single or multi channel mode TRANSIENTS Capturing: >20 µs transient detectability Trigger: Level, slope, manual Buffer: min. 10 periods of pre / post size, up to 1000 periods can be recorded Channels: 3 x U, 3 X I, single or multi channel mode A 1037 A 1039 A 1069 A 1099 A 1100 A 1101 A 1120 A 1122 A 1124 A 1171 S 2014 S 2015 A 1171 S 2014 A 1069, A 1122 A 1101 S 2015 - Three-phase current transformer 5 A/1 V - Clamp adapter - Mini current clamp 100 A /1 V - Single-phase flex, current clamp 3000 A /1 V - Modem ST - Modem GSM - Three-phase flex, current clamp 3000 A /1 V - Mini current clamp 5 A /1 V - Modem Entrance Key (MI 2092) - USB/RS232 converter with 1 m fixed cable - Safety fuse adapters - Safety flat clamps General Display: Graphic Liquid Crystal Display with LED backlight, 160 x 116 dots resolution NON – VOLATILE MEMORY 2048 Kbytes SRAM, battery backed. DIGITAL HARDWARE SPECIFICATION A/D conversion, 14 bit with 128 samples per channel per period (43–68 Hz). OUTPUTS Communication type: RS 232 serial interface, fully opto isolated Baud rate: 2400–57600 bps Connector: 9 pin D-type. Communication cable: Standard type POWER SUPPLY Operating range: 230 V A.C. +10 % – 20 %, 45–65 Hz, 8 VA Optional: 115 V A.C. +10 % – 20 %, 45–65 Hz, 8 VA DC power supply: Internal 4 x 1.2 V NiCd or NiMh rechargeable IEC LR14 batteries provide full operation for up to 5 hours Charger: Internal built-in battery charger, charging time approx. 10 hours GENERAL Working temperature range: –20 °C … + 60 °C Max. humidity: 85 % RH (0 ¸ 40 °C) Pollution degree: 2 Protection classification: II - double insulation Overvoltage category: Voltage inputs: CAT III 600 V; optional CAT IV 600 V AC power supply CAT III 300 V Protection degree: IP 64 Dimensions: 265 x 110 x 185 mm Weight (without accessories): 2 kg 7