Download MX2 Users Manual
Transcript
"C" Group: Intelligent Terminal Functions Option Code Terminal Symbol 21 ZS Section 3-7 Output Function Summary Table Function Name Description Zero Hz Speed Detection Signal ON OFF 22 DSE Speed Deviation Exces- ON sive OFF 23 POK Positioning Completion 24 FA4 Frequency Arrival Type 4-Over frequency ON OFF ON OFF 25 FA5 Frequency Arrival Type 5-Set frequency ON OFF 26 OL2 Overload Advance Notice Signal 2 ON OFF 27 ODc 28 OIDc 31 FBV Analog Voltage Input Disconnect Detection Analog Current input Disconnect Detection ON OFF ON OFF PID Second Stage Out- ON put OFF 32 NDc Network Disconnect Detection ON OFF 33 LOG1 Logic Output Function 1 ON OFF 34 LOG2 Logic Output Function 2 ON OFF 35 LOG3 Logic Output Function 3 ON OFF 138 39 WAC Capacitor Life Warning Signal 40 WAF Cooling Fan Warning Signal ON OFF ON OFF Output frequency falls below the threshold specified in C063 Output frequency is higher than the threshold specified in C063 Deviation of speed command and actual speed exceeds the specified value P027. Deviation of speed command and actual speed does not exceed the specified value P027. Positioning is completed Positioning is not completed When output to motor is at or above the set freq., even if in accel (C045) or decel (C046) ramps When output to motor is OFF, or at a level below the set frequency When output to motor is at the set frequency, during accel (C045) and decel (C046). When output to motor is OFF, or is not at a level of the set frequency When output current is more than the set threshold (C111) for the overload signal When output current is less than the set threshold for the deviation signal When the [O] input value < B070 setting (signal loss detected) When no signal loss is detected When the [OI] input value < B071 setting (signal loss detected) When no signal loss is detected Transitions to ON when the inverter is in RUN Mode and the PID Process Variable (PV) is less than the Feedback Low Limit (C053) Transitions to OFF when the PID Process Variable (PV) exceeds the PID High Limit (C052), and transitions to OFF when the inverter goes from Run Mode to Stop Mode When the communications watchdog timer (period specified by C077) has time out When the communications watchdog timer is satisfied by regular communications activity When the Boolean operation specified by C143 has a logical "1" result When the Boolean operation specified by C143 has a logical "0" result When the Boolean operation specified by C146 has a logical "1" result When the Boolean operation specified by C146 has a logical "0" result When the Boolean operation specified by C149 has a logical "1" result When the Boolean operation specified by C149 has a logical "0" result Lifetime of internal capacitor has expired. Lifetime of internal capacitor has not expired. Lifetime of cooling fan has expired. Lifetime of cooling fan has not expired.