"C" Group: Intelligent Terminal Functions
Option
Code
Terminal
Symbol
21
ZS
Section 3-7
Output Function Summary Table
Function Name
Description
Zero Hz Speed Detection Signal
ON
OFF
22
DSE
Speed Deviation Exces- ON
sive
OFF
23
POK
Positioning Completion
24
FA4
Frequency Arrival Type
4-Over frequency
ON
OFF
ON
OFF
25
FA5
Frequency Arrival Type
5-Set frequency
ON
OFF
26
OL2
Overload Advance
Notice Signal 2
ON
OFF
27
ODc
28
OIDc
31
FBV
Analog Voltage Input
Disconnect Detection
Analog Current input
Disconnect Detection
ON
OFF
ON
OFF
PID Second Stage Out- ON
put
OFF
32
NDc
Network Disconnect
Detection
ON
OFF
33
LOG1
Logic Output Function 1 ON
OFF
34
LOG2
Logic Output Function 2 ON
OFF
35
LOG3
Logic Output Function 3 ON
OFF
138
39
WAC
Capacitor Life Warning
Signal
40
WAF
Cooling Fan Warning
Signal
ON
OFF
ON
OFF
Output frequency falls below the threshold specified
in C063
Output frequency is higher than the threshold specified in C063
Deviation of speed command and actual speed
exceeds the specified value P027.
Deviation of speed command and actual speed does
not exceed the specified value P027.
Positioning is completed
Positioning is not completed
When output to motor is at or above the set freq.,
even if in accel (C045) or decel (C046) ramps
When output to motor is OFF, or at a level below the
set frequency
When output to motor is at the set frequency, during
accel (C045) and decel (C046).
When output to motor is OFF, or is not at a level of
the set frequency
When output current is more than the set threshold
(C111) for the overload signal
When output current is less than the set threshold for
the deviation signal
When the [O] input value < B070 setting (signal loss
detected)
When no signal loss is detected
When the [OI] input value < B071 setting (signal loss
detected)
When no signal loss is detected
Transitions to ON when the inverter is in RUN Mode
and the PID Process Variable (PV) is less than the
Feedback Low Limit (C053)
Transitions to OFF when the PID Process Variable
(PV) exceeds the PID High Limit (C052), and transitions to OFF when the inverter goes from Run Mode
to Stop Mode
When the communications watchdog timer (period
specified by C077) has time out
When the communications watchdog timer is satisfied by regular communications activity
When the Boolean operation specified by C143 has a
logical "1" result
When the Boolean operation specified by C143 has a
logical "0" result
When the Boolean operation specified by C146 has a
logical "1" result
When the Boolean operation specified by C146 has a
logical "0" result
When the Boolean operation specified by C149 has a
logical "1" result
When the Boolean operation specified by C149 has a
logical "0" result
Lifetime of internal capacitor has expired.
Lifetime of internal capacitor has not expired.
Lifetime of cooling fan has expired.
Lifetime of cooling fan has not expired.