Section 7-1
PLC Setup
Pulse Output 0 Origin Search/Return Initial Speed
Programming
Console setting
address
Word
Bit
258
259
Settings
00 to 15 00000000 to
00 to 15 000186A0 hex
(See note.)
Default
00000000
hex
Function
Related
Auxiliary
Area flags/
bits
Specifies the starting speed (0 to
--100,000 pps) for the pulse output 0
origin search and origin return operations.
Time when
setting is read
by CPU Unit
At start of operation
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 0 Origin Search High Speed
Programming
Console setting
address
Word
Bit
260
261
Settings
00 to 15 00000001 to
00 to 15 000186A0 hex
(See note.)
Default
00000000
hex
Function
Related
Auxiliary
Area flags/
bits
Specifies the high speed setting (1 to --100,000 pps) for pulse output 0 origin
search operation.
Time when
setting is read
by CPU Unit
At start of operation
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 0 Origin Search Proximity Speed
Programming
Console setting
address
Word
Bit
262
263
Settings
00 to 15 00000001 to
00 to 15 000186A0 hex
(See note.)
Default
Function
00000000
hex
Specifies the proximity speed setting
(1 to 100,000 pps) for pulse output 0
origin search operation.
Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
At start of operation
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 0 Search Compensation Value (Origin Compensation)
Programming
Console setting
address
Word
264
265
Settings
Bit
00 to 15 80000000 to
00 to 15 7FFFFFFF hex
(See note.)
Default
---
Function
Sets the pulse output 0 origin compensation (-2,147,483,648 to
2,147,483,647).
Related
Auxiliary
Area flags/
bits
---
Time when
setting is read
by CPU Unit
At start of operation
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
221