Download Flex Network High-Speed Counter Unit User Manual
Transcript
Chapter 5 – Data Settings Data Setting Procedures Write Read 1. Set WD register to a value. 2. Enter a Write command in the CMD register. 1. Enter a Read command in the CMD register. Data is written to the High-speed Counter unit. Data is read from the High-speed Counter unit to the RD register. High Speed Counter Command Flow Data Write to Ring Counter Upper/Lower Limit Values 1) Change to Setting Mode (CTL bits 14, 15) Status Check (STA bits 14, 15) Setting Mode RUN Mode 2) A 6) Reflected in Status (STA) Setting Mode RUN Mode 3) Ring counter Upper Limit or Lower Input of Ring Counter Upper Limit Limit WD (Integer) or Lower Limit (Integer) Since the upper limit and lower limit cannot be input at the same time, you will need to repeat certain operations. 3: Counter 1 Lower limit 4: Counter2 Upper limit 5: Counter 2 Lower limit 6: Counter 2 Upper limit 4) Ring Counter Upper limit/Lower limit 0 Clear Command Send/CMD A 5) Command Complete Check/ Status (bit 13) Check new Ring Counter value/RD Ring Counter Value Depending on the driver used, when the next command is issued, this will turn OFF. The Flex Network Driver contains the RESET signal. All setting and resetting of all other signals is performed via the user’s software. Flex Network High-Speed Counter Unit User Manual 5–7