Download MODBUS(R) Interface Module User`s Manual
Transcript
4 MODBUS(R) STANDARD FUNCTIONS (1) Request message format (Master Function code Function code (08H) Slave) Sub-function code Sub-function code (0001H) Data Clear setting of Communications event log 0000H: Not clear FF00H: Clear (H) (L) (H) (L) Figure 4.30 Restart communications option (Request message) (2) Response message format (Slave Master) (When completed normally) The slave returns the request message received from the master without change. However, if a request message is received during listen only mode, the status will only return to online mode and no response message will be returned. (When completed with an error) Function code Function code (88H) Data Exception code*1 Figure 4.31 Restart communications option (Exception message) * 1 Exception and error codes are stored in the buffer memory in the case of error completion. Refer to the following for storage location, confirmation methods, and detailed contents. Section 11.4 4 - 27 4.11 Diagnostics (FC:08) 4.11.2 Restart communications option (sub-function code: 01)