Download DAQSTATION CX1000/CX2000 Communication Interface
Transcript
7.3 Output Format of BINARY Data Event Data • The MI command is used to output the FIFO data. • The ID number of the output format is “12.” See “Identifier” on page 7-3. Header Block 1 ... Block n BINARY data (The BINARY data section on the “Conceptual diagram” on page 7-2.) Header Same as the “Header” for the display data. Block 2 bytes Measured data ... ... Computed data ... ... Control data ... ... 4 bytes Special Data Values The measured/computed/control data take on the following values under special conditions. Special Data Value Type Measured/Control Data Computed Data + Over – Over Skip Error Undefined 7FFFH 8001H 8002H 8004H 8005H 7FFF7FFFH 80018001H 80028002H 80048004H 80058005H Note The measured/computed/control data is output according to the byte order specified with the BO command. Manual Sampled Data • The ME or MO command is used to output the data. • The ID number of the output format is “4.” See “Identifier” on page 7-3. • For a description of the data format, see the user’s manual IM 04L31A01-01E or IM 04L31A01-03E. Report Data (Hourly, Daily, Weekly, and Monthly) • The ME or MO command is used to output the data. • The ID number of the output format is “5” for the hourly data, “6” for the daily data, “7” for the weekly data, and “8” for the monthly data. See “Identifier” on page 7-3. • For a description of the data format, see the user’s manual IM 04L31A01-01E or IM 04L31A01-03E. 7-30 IM 04L31A01-17E